Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM08230
Parcel: 140420120

Address:
7005 S PLUMER AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM08230
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2016 MARTIN BROWN FIRE REVIEW Approved
04/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/12/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/12/2016 ROBERT SHERRY WATER REVIEW Completed
04/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/19/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Plan Sheet E401, E401.1 and E 505.
(a). Keynotes on sheet 401.1 call out for 2500 Amp rated equipment. Seems to be in conflict with the keynotes on the one line diagram on plan sheet E505 calls out 3000 Amp gear for the same equipment.
#2. Ref: Plan Sheet E506.
(a). Please clarify how Keynote #11 ( plan sheet E506), shown on the one line correlates with the equipment shown on plan sheet E503. As referred by keynote #11.
(b). Identify the 400 amp panel indicated by keynote #6.
#3. Ref: Plan Sheet E414.1.
(a). It appears there are no egress doorways in the main electrical room B1-101. Please address this and verify code compliance with art. 110.26C 2011 NEC.
#4. Provide for a Selective Coordination Analysis to be submitted to the AHJ as required per NEC art's 620, 700, 701, 708.
Ref: IBC sec. 107.2.1 and 2011 NEC.
04/25/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved