Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM06798
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/25/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/25/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
11/27/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The heating and cooling load calculations were not found in this submittal. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.] 2. An automatic start capability is not the same as "programmable occupied/unoccupied times". See Section C403.2.4.3.3, IECC 2012. [Initial comment: Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012.] 3. Exception 4 of Section 403.2.1, IMC 2012 does allow the supply air stream to include up to 10% of the exhausted air from the restrooms but the system you propose would not add the recirculated air from the restrooms to the supply air stream until after the egress corridor had been used as a duct. Reference: Section 601.2, IMC 2012. [Initial comment: Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fans shall operate when HVAC air is supplied to the restrooms, not just when the restroom is occupied). Reference: Section 403.2.1 (4), IMC 2012.] |
12/03/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/08/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. #1. As per the last electrical plan review, it was requested to provide full compliance with the Tucson Outdoor Lighting Code. The Tucson / Pima County Outdoor Lighting Code can be downloaded from www.tucsonaz.gov/pdsd. The information as required in section 104 of this code must be included in the plan documents for approval. Ref: IBC 107.2.1, Tucson / Pima County Outdoor Lighting Code. |