Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM06580
Parcel: 13321074A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM06580
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Add a note to your fixture schedule stating that the sensor-operated faucets will be set to operate for at least 10-seconds and no longer than 30-seconds (0.25 Gallons).][Initial comment: Verify that the specified faucet for the lavatories will automatically dispense a maximum of 0.25 gallons per metering cycle and will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]
11/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an expiration date on sheets M002 and M102. [Second comment: Provide the expiration date on sheets M002 and M102.] [Initial comment: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).]
2. The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2012 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide justification for the use of a Zone Air Distribution Effectiveness (Ez) of 1.0 for a ceiling supply, ceiling return using a gas-fired furnace. Reference: Section 403.3.1.2, IMC 2012. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.]
3. The City of Tucson has not adopted ASHRAE Standard 62-1 as an approved method for calculating ventilation requirements. Table 403.3 provides a category of "Dressing rooms" under the general occupancy classification of "Retail stores, sales floors and showroom floors"; no locker rooms are included in this occupancy classification. "Locker rooms" and "Sports locker rooms" are found under the education occupancy classification. [Initial comment: Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.]
11/27/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/02/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2015 AROMERO4 APPROVAL SHELF Completed
12/04/2015 AROMERO4 OUT TO CUSTOMER Completed
12/04/2015 AROMERO4 REJECT SHELF Completed