Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM06580
Parcel: 13321074A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM06580
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2015 STEVE SHIELDS ZONING REVIEW Approved
09/29/2015 MARTIN BROWN FIRE REVIEW Approved
10/14/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A002; CODE SUMMARY: PLEASE PROVIDE THE CALCULATION ON THIS SHEET FOR THE ALLOWABLE AREA FOR THIS PROJECT (LISTED AS 39,728 SF).
2. SHEET A002; CODE SUMMARY: THE ACTUAL BUILDING AREA IS LISTED AS 25,185 SF (GENERAL/AREA), AND ALSO AS 24,185 SF (MEANS OF EGRESS). PLEASE CLARIFY.
3. SHEET A002; CODE SUMMARY: PLEASE VERIFY ON THE DRAWINGS THE NUMBER OF ACCESSIBLE ENTRANCES MEETS THE REQUIREMENTS OF THE IBC SECTION 1105.1.
4. SHEET A212; MAP: PLEASE FINISH THE MONUMENT SIGN INDICATORS ON THE PLAN (TWO THUS).
5. SHEET A410; PLAN A3: THE BENCH WIDTH INDICATES 2'-0" MINIMUM ON THE PLAN. SECTION 903.3 OF THE ICC/ANSI INDICATES 20" MINIMUM AND 24" MAXIMUM DEPTH. PLEASE REVISE THE DRAWING PLAN A3 AND DETAIL A1(A).
6. STRUCTURAL CALCULATIONS; BRODERICK ENGINEERING: THESE CALCULATIONS ARE BEING SUBMITTED FOR WHAT PURPOSE? THIS PERMIT IS FOR A TENANT IMPROVEMENT TO A BUILDING, WHILE THE BRODERICK ENGINEERING CALCULATIONS ARE FOR THE ACTUAL BUILDING DESIGN. PLEASE VERIFY.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/14/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
10/15/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified faucet for the lavatories will automatically dispense a maximum of 0.25 gallons per metering cycle and will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
2. Verify that the pipe sizes called out for the flush valves for the water closets will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012.
3. Verify that all of the vents located within the building rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. the floor drain in the maintenance room has a vent that runs horizontally below the flood rim of the floor drain). Reference: Section 905.4, IPC 2012.
10/15/2015 ROBERT SHERRY WATER REVIEW Completed
10/16/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. In the previously submitted COMcheck Envelope Compliance Certificate, the high efficiency HVAC option was selected as the additional efficiency package requirement to comply with Section C406, IECC 2012. However, no additional efficiency package requirement has been identified in either the Mechanical or Interior Lighting Compliance Certificates. Either the Mechanical Compliance Certificate or the Interior Lighting Compliance Certificate will need to be revised to comply with Section C406, IECC 2012.
4. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. The roof drains on this building terminate at the building walls. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
5. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
6. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.
7. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012.
10/21/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review.