Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM05938
Parcel: 123120540

Address:
1111 E SENECA ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T15CM05938
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2016 KROBLES1 ENGINEERING REVIEW Needs Review
01/20/2016 KROBLES1 BUILDING-RESIDENTIAL REVIEW Needs Review
09/04/2015 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

FROM: Steve Shields,
Lead Planner


PROJECT:
T15CM05938
1111 E. Seneca Street
Detached ramada, shed #2 and existing storage/craft building.

TRANSMITTAL: September 11, 2015


COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the NR-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

Neighborhood Preservation Zone (NPZ), Jefferson Park, review and approval is required prior to approval of the plans.

Accessory structures shall not exceed 12 feet in height, unless attached to a principal structure. If attached to the principal structure, maximum height permitted shall be the same as for the principal structure. (UDC Section 6.3.3.C). Proposed ramada building height as measured per UDC Section 6.4.4 is 14'-2"

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 13'-0" the required perimeter yard setback from the ramada to the east property line is 8'-8", proposed perimeter yard setback is 4'-0".

Based on a wall height of 8'-2" the required perimeter yard setback from the Shed #2 building to the North property line is 6'-0", proposed perimeter yard setback is 2'-0".

Based on a wall height of 11'-0" the required perimeter yard setback from the Shed #2 building to the East property line is 7'-4", proposed perimeter yard setback is 4'-0".
09/04/2015 SSHIELD1 NPPO REVIEW Passed