Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide conduit and conductor sizes for the elevator feeders, ( ckts 25,27 ).
03/07/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a sump pump or drain for the elevator pit to prevent the accumulation of water. Reference: Section 3001.2, IBC 2012 (and ASME A17.1).
03/07/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide information to show that the elevator machine room does not require an independent venting or air conditioning system to prevent overheating of the elevator equipment. Reference: Section 3006.2, IBC 2012.