Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T15CM05806
Parcel: 11713177A

Address:
201 S STONE AV 4

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM05806
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide conduit and conductor sizes for the elevator feeders, ( ckts 25,27 ).
03/07/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a sump pump or drain for the elevator pit to prevent the accumulation of water. Reference: Section 3001.2, IBC 2012 (and ASME A17.1).
03/07/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide information to show that the elevator machine room does not require an independent venting or air conditioning system to prevent overheating of the elevator equipment. Reference: Section 3006.2, IBC 2012.