Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T15CM05806
Parcel: 11713177A

Address:
201 S STONE AV 4

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM05806
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/06/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The minimum dimension for a scupper is 4". Provide secondary (overflow) roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012. [Second comment: Comment not addressed by the architect.] [Initial comment: Clarify the meaning of the scupper calculation shown on 1/A3.0.]
12/29/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change
12/30/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Stone Avenue Homes
T15CM05802, T15CM05804, T15CM05805, T15CM05806, T15CM05807 & T15CM05808
Building Plans (3rd Review)

TRANSMITTAL DATE: December 30, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning cannot approve the building plans until approved and stamped by IID section.

3. Zoning cannot approve until all PDSD agencies have approved all building plans.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956