Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM05191
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/27/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/03/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/05/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. #1. As per the previous plan review comment, "Please address electrical plan review comment #1 from the last plan review 8/21/15. The Tucson / Pima County Outdoor Lighting Code can be downloaded on line www.tucsonaz.gov/pdsd." there is still no compliance per Chapter 4, ( Lumen calc's ), and sec. 402.1 "Rated Color Temperature Output", of the Tucson / Pima County Outdoor Lighting Code. Be advised that the COMCHECK for exterior lighting does not address the Tucson Outdoor Lighting Code. |