Permit Number: T15CM05191
Parcel: 127121200

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM05191
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change Please calculate the occupant load per the IBC/IFC. Use the table in Chapter 10 for the areas that are not fixed seating, then add in the fixed seating area. The customer pick-up area is larger than the 42 square feet listed on the resubmittal.
10/09/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/09/2015 ROBERT SHERRY WATER REVIEW Completed
10/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/09/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 16; SHEET S3: THE CITY OF TUCSON REQUIREMENT FOR LETTERING HEIGHT WAS NOT MET IN VARIOUS DETAILS AND TABLES ON SHEET S3. PLEASE REVISE.
2. PREVIOUS COMMENT 17: THE NORTH ARROWS ON SHEETS S4 AND S5 DO NOT MATCH THE NORTH ARROWS ON THE ARCHITECTURAL DRAWINGS. PLEASE COORDINATE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/15/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address electrical plan review comment #1 from the last plan review 8/21/15. The Tucson / Pima County Outdoor Lighting Code can be downloaded on line www.tucsonaz.gov/pdsd.