Permit Number - T15CM05191
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Please calculate the occupant load per the IBC/IFC. Use the table in Chapter 10 for the areas that are not fixed seating, then add in the fixed seating area. The customer pick-up area is larger than the 42 square feet listed on the resubmittal. |
| 10/09/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/09/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/09/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 16; SHEET S3: THE CITY OF TUCSON REQUIREMENT FOR LETTERING HEIGHT WAS NOT MET IN VARIOUS DETAILS AND TABLES ON SHEET S3. PLEASE REVISE. 2. PREVIOUS COMMENT 17: THE NORTH ARROWS ON SHEETS S4 AND S5 DO NOT MATCH THE NORTH ARROWS ON THE ARCHITECTURAL DRAWINGS. PLEASE COORDINATE. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |