Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T15CM05191
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2015 | MARTIN BROWN | FIRE | REVIEW | Needs Review | 1. PLEASE REVISE OCCUPANT LOAD CALCULATION TO INCLUDE THE CUSTOMER PICK UP AREA. 2. IS ALL OF THE SEATING "FIXED"?-KENB |
08/12/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET CS1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE ABBREVIATIONS. 2. SHEET CS2; DETAIL 2: PLEASE ADD THE VERTICAL GRAB BAR TO THE TOILET ELEVATION PER THE ICC/ANSI FIGURE 604.5.1. 3. SHEET CS3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES. 4. SHEET A1; FLOOR PLAN: KEY NOTE 19 REFERENCES 5/A13 FOR THE MAGNETIC MARKETING BOARDS. PLEASE REVISE THE REFERENCE. 5. SHEET A1; FLOOR PLAN: PLEASE INDICATE ON THE PLAN THE DISTANCE BETWEEN THE TWO EXIT DOORS ON THE NORTH AND SOUTH WALLS MEET THE REQUIREMENTS OF THE IBC SECTION 1015.2.1. 6. SHEETS A1, A2, AND A3; FLOOR PLANS: PLEASE PROVIDE A NORTH ARROW ON THE PLANS. 7. SHEET A1; FLOOR PLAN: PLEASE INDICATE ON THE SHEET THE NUMBER OF ACCESSIBLE SEATING SPACES PER THE IBC SECTION 1009.11, AND SHOW THOSE SPACES ON THE FLOOR PLAN. 8. SHEET A1 (FLOOR PLAN); SHEET A9 (DETAIL 5): DETAIL 5/A9 INDICATES 'NOT USED', BUT THE DINING AREA HAS THAT DETAIL CUT ON THE PLAN. PLEASE CLARIFY. 9. SHEET A1 (FLOOR PLAN); SHEET A9 (DETAIL 15): DETAIL 15/A9 INDICATES 'NOT USED', BUT THE DINING AREA HAS THAT DETAIL CUT ON THE PLAN. PLEASE CLARIFY. 10. SHEET A5: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE DETAIL 3. 11. SHEET A9: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE DETAIL 11. 12. SHEET A12; RESTROOM ELEVATIONS 1 AND 2: PLEASE ADD THE VERTICAL GRAB BAR TO THE WOMEN'S RESTROOM ELEVATION C AND THE MEN'S RESTROOM ELEVATION D PER THE ICC/ANSI FIGURE 604.5.1. 13. SHEET S1; STRUCTURAL SPECIFICATIONS SHEET (CONCRETE NOTES): THE NOTES INDICATE THE CONCRETE STRENGTH FOR A POST TENSIONED SLAB. PLEASE REMOVE THAT SPECIFICATION. 14. SHEET S1; STRUCTURAL SPECIFICATIONS SHEET (DESIGN NOTES): THE CITY OF TUCSON AMENDMENTS TO THE 2012 IBC (1609.5.1.1) REQUIRES A 115 MPH ULTIMATE WIND SPEED AND CORRESPONDING 90 MPH NOMINAL WIND SPEED. PLEASE REVISE THE NOTES AND CALCULATIONS AS REQUIRED. 15. SHEET S2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE VARIOUS DETAILS. 16. SHEET S3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE VARIOUS DETAILS AND TABLES. 17. SHEETS S4 AND S5: PLEASE PROVIDE NORTH ARROWS ON THE PLANS. 18. SHEET S4 (FOUNDATION PLAN); SHEET S5 (ROOF FRAMING PLAN): AT THE TRELLIS ON THE WEST SIDE, A NOTE ON THE FOUNDATION PLAN AT THE COLUMNS INDICATES AN ALUMINUM TUBE, WHILE A NOTE ON THE ROOF FRAMING PLAN AT THE COLUMNS INDICATES A 4" SQUARE STANDARD PIPE COLUMN. PLEASE CLARIFY. 19. SHEET S5: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE ROOF FRAMING DRAWING NOTES. 20. SHEET S5 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (TRELLIS DESIGN): WHERE DO THE JOISTS AND BEAM FROM THE CALCULATIONS SHOW UP ON THE FRAMING PLAN? A NOTE ON THE PLAN INDICATES 'TRELLIS BY OTHERS'. PLEASE CLARIFY. 21. STRUCTURAL CALCULATIONS; TRASH ENCLOSURE: THE CALCULATION INDICATES TO 'SEE PRINT OUT FOR WALL'. WHERE IS THAT PRINT OUT? 22. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
08/13/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
08/18/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. The 2012 International Mechanical Code with Local Amendments is the relevant code for this project, not the 2009 UMC or the 2010 CMC. 3. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 4. Show how the "Additional Efficiency Package Requirements" noted in COMcheck (C406, IECC 2012) is to be accomplished. Reference: Section C401.2, IECC 2012. 5. Revise the lighting and mechanical COMcheck reports to indicate "new construction", not an addition to an existing building. 6. Provide NFRC fenestration product ratings for the Solar Heat Gain Coefficient (SHGC) on COMcheck or use the appropriate default SHGC from Table C303.1.3 (2), IECC 2012. Coordinate the SHGC values shown on the COMcheck Envelope Compliance Certificate with the window descriptions shown on the drawings (i.e. the required SHGC on the submitted COMcheck is 0.25 but it is "0.40 or lower" on sheet A11.0). Reference: Section C303.1.3, IEC 2012. 7. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 8. Coordinate the exhaust fan schedule with the proposed Type I hoods. Reference: Section 107.2.1, IBC 2012. 9. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. |
08/18/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The reference civil utilities drawing, 3 of 6, is out of date and needs to be replaced with the current version. 2. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 3. The Minimum Plumbing Fixtures calculation on sheet P-1 appears to be from the UPC. Use the current code (2012 IBC) and coordinate with the architect if this calculation is to be retained. 4. The 2012 International Plumbing Code has been adopted by the City of Tucson. Revise the plumbing design and notes to comply with this code. 5. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Verify that the specified mixing valve conforms to ASSE 1070. Reference: Section 607.1.2, IPC 2012. 6. Provide automatic faucets for the restroom lavatories that will be set to dispense a maximum of 0.25 gallons per metering cycle and will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 7. Clarify the note on the water heater detail on sheet P-1 that states in part, "… Discharge outside of building valve outlet to terminate within 18" of grade." Discharge piping for a combination temperature and pressure relief valve shall not have any valves. Reference: Section 504.6 (12), IPC 2012. 8. Appliances (e.g. beverage dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 9. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 10. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. 11. Provide roof drainage calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. One note on sheet P6 states that the roof drain sizes are based on a rainfall rate of 2" per hour and the 2013 CPC while another note on the same sheet states that the calculations are based on a rainfall rate of 4" per hour. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012. 12. Clarify the connected loads or input ratings for each appliance. Southwest Gas, the local gas utility provides natural gas with an energy content of approximately 1,000 BTU per cubic foot, not 1100 BTU per cubic foot as shown in the gas isometric on sheet P8. Reference: Section 402.1, IFGC 2012. 13. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Reference: Section 402.1, IFGC 2012. 14. Correct the size of the gas piping branch serving the four broilers and the rethermalizer as shown in the gas isometric on sheet P8: the total load appears to be 1190 MBH, not 207 MBH. 15. Clarify the termination of the flue for the water heater. Detail 1/P5 shows it terminating above the roof and 8-feet from the parapet wall while the gas plumbing plan calls for the flue to terminate on the west wall of the building. (Clarify also the symbol that is shown located in the northwest corner of the roof on sheet P6, near the intake of the makeup air unit.) |
08/18/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the estimated water demand for this building to verify that the proposed water meter is correctly sized. Tucson Water requires the use of Appendix E, 2012 IPC as the basis for the calculations. |
08/21/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide the following information; #1. Full compliance with the Tucson/ Pima County Outdoor Lighting Code for thr exterior lighting. #2. Lettering Font size for plan submittal is 3/32" min. Plan Sheet E1 and E6. #3. Show conduit, conductor, sizes and types for the secondary service conductors between the electrical service equipment and the utility transformer. Plan sheet E5 ( one line ). Ref: IBC 107.2.1, NEC, City of Tucson Plan Submittal Requirements. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/23/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |