Permit Number: T15CM05114
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM05114
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2015 LOREN MAKUS ENGINEERING REVIEW Approved
07/24/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
07/27/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Please provide for disconnecting means within site of transformer T1, for the primary feeder, or provide field marking on the transformer and lockable disconnect switch as required per NEC art. 450. 14.
#2. Please provide a complete panel schedule including load calc's for existing panel A.
#3. Please verify voltages for both transformers shown as step down.
#4. Please show the conduit, conductor, sizes and types for all the receptacles shown that are new, existing, or refed to the new panel L1.
07/27/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.0: PLEASE REVISE THE ELECTRICAL DRAWING NUMBERS IN THE INDEX TO MATCH THE DRAWINGS PROVIDED.
2. SHEET A1.0D: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE SPECIFICATIONS.
3. SHEET A1.0; KEYNOTES: NOTE 5 INDICATES AN ADA RAMP WITH A MAXIMUM SLOPE OF 1:8 PER 15.1.4 EXCEPTIONS 1 AND 2. PLEASE PROVIDE WHICH CODE THIS REFERENCES. THE ACCESSIBILITY ON THIS PROJECT FALLS UNDER THE 2010 ADAAG.
4. SHEET A1.0; KEYNOTES: NOTE 15 REFERENCES A NEW WOOD CANOPY. IS THIS PART OF THIS PROJECT? IF SO, PROVIDE STRUCTURAL CALCULATIONS, DRAWINGS, AND SPECIFICATIONS FOR THE CANOPY.
5. SHEET A3.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE SPECIFICATIONS.
6. SHEET S1.0; DETAIL 101: NOTES INDICATE DRAWING REVISIONS ON 7/13/15. PLEASE CLARIFY.
7. GENERAL: PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE CAROUSEL FOUNDATION DESIGN.
8. GENERAL: IS ANY NEW SITE LIGHTING REQUIRED FOR THIS PROJECT? IF SO, PLEASE INDICATE ON THE PLANS. PROVIDE FOUNDATION DETAILS AND CALCULATIONS AS REQUIRED.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/27/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2015 AROMERO4 OUT TO CUSTOMER Completed