Permit Number: T15CM05010
Parcel: 132130720

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM05010
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change It appears that all of sections 605.11.3.3.2 and 605.11.3.3.3 are not being provided for on the plans.
08/10/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change STRUCTURAL REVIEW COMPLETED. STAMPED APPROVAL PENDING COMPLIANCE WITH FIRE AND ELECTRICAL REVIEWS
08/12/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please clarify or change the keynote #10 on plan sheet 'PV14', indicates to utilize the warning label per detail #11 from warning label plan sheet (PV17). Detail #11 is blank?

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2015 AROMERO4 OUT TO CUSTOMER Completed