Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03555
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/30/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Restroom exhaust fans to run during business hours, connecting to the light switch will not comply with mechanical code see note #7 Plan Sheet M2. |
06/30/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Tucson Water limits a 5/8" water meter to a maximum demand of 15 GPM. A demand of 18 GPM will require the installation of a 3/4" water meter. [Initial comment: Provide the size and serial number of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.] |
06/30/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the addition of the reduced pressure backflow prevention assembly will not adversely affect the minimum residual pressure of 15 PSI for the fixtures in this suite. |
06/30/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/09/2015 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review |