06/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Verify that the automatic faucets specified for the lavatories will be set to dispense a maximum of 0.25 gallons per metering cycle and will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
06/09/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size and serial number of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.
06/09/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Revise the HVAC unit controls to have an automatic start capability (this is not the same as a programmed start time). Reference: Section C403.2.4.3.3, IECC 2012.
4. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the supply air is to be exhausted during the store's operating hours even if the restroom lights are turned off). Reference: Section 403.2.1 (4), IMC 2012.
06/15/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following discrepancies on Plan Sheet E2.0.
#1. The electrical system voltages shown at the existing service term can and the new loadcenter 'A' on Detail 2 ( one line diagram ) seem to be in conflict. Also the one line diagram does not coincide with the service equipment lay-out on the floorplan.
#2. Provide a complete fault current analysis.
06/25/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G0.0; SHEET INDEX: THE INDEX INDICATES TWO STRUCTURAL SHEETS IN THIS SET (S1 AND S2). PLEASE PROVIDE OR REVISE THE INDEX.
2. SHEET A3.1; SECTION 01: THE SECTION AND DETAILS ON THIS SHEET REFERENCE STRUCTURAL (NO STRUCTURAL SHEETS PROVIDED). PLEASE VERIFY.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.