Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM03386
Parcel: 11506207B

Address:
1801 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03386
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. Panic Hardware is required for all exit doors. Please revise drawings.
2. Indicate that a manual fire alarm system will be installed.
3. Indicate the covering for the patio area and that it will be protected with the fire sprinkler system.
06/04/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review.
06/08/2015 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
Principal Planner

PROJECT: T15CM03386
1801 N Stone Avenue
Brother John's BBQ Restaurant

TRANSMITTAL DATE: June 8, 2015

DUE DATE: June 22, 2015

COMMENTS:

01. Zoning has reviewed the building plans for the Interior T.I and outside work for compliance with the DP. While the building plans appear to be in substantial compliance with the unapproved DP zoning cannot approve the building plans at this time.



02. Zoning has also reviewed the DP concurrently with the building plan package. Zoning will continue to review both the DP and building plans for consistency. Once the DP is approved zoning can approve the building plans.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
06/10/2015 ROBERT SHERRY WATER REVIEW Completed
06/10/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.
2. Correct the plumbing calculations on sheet A0.0: 2.33 water closets for males and 2.33 water closets for females is to be rounded up to 3 water closets for each sex. With a total requirement of 6 water closets, a family restroom is required in an assembly occupancy. Reference: Footnote (a), Table 2902.1 and Section 1109.2.1, IBC 2012
3. The existing 2" horizontal branch of the building drain that serves the two floor drains in the kitchen is shown being connected to the new grease waste. Clarify how the continuation of the 2" branch beyond the new connection point (i.e. west of the new connection) is to be taken out of service and show how the existing 3" building drain will be provided with a 3" cleanout. Reference: Section 107.2.1, IBC 2012 and Section 708.7, IPC 2012.
4. The existing cleanout for the 2" horizontal branch of the building drain running through the kitchen appears like it will be obstructed by one of the new smokers; show how the cleanout will be either relocated or made accessible. Reference: Sections 708.4, 708.8, and 708.9, IPC 2012.
06/11/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
2. Provide the manufacturer's installation information that shows the proposed smokers are listed and labeled for the proposed exterior installation with no hood. Show that the penetration of the exterior wall maintains the required clearances to combustibles. Reference: Section 301.7, IMC 2012.
3. The proposed 18" diameter exhaust ducts for the proposed smokers will be conveying smoke and grease-laden air. Provide details for the duct showing how the ducts will be constructed, maintained and supported. Show how the building will be protected from a grease fire in the ducts. Reference: Section 506, IMC 2012.
4. Explain the purpose of EF-4 and show how the air pressure in the kitchen will be maintained positive with respect to the exterior of the building. Reference: Section 508.1, IMC 2012.
06/22/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN REVIEW COMMENTS
6-23-15
T15CM03386
1801 N. Stone Ave.
Metro TED

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

1. Please define the limits of the proposed patio area and provide a maximum occupancy calculation to supplement the occupancy areas indicated inside the building. Note: these occupancy modifications may impact the minimum number of required plumbing fixtures and/or the requirement for a family/assisted use toilet room, 1109.2.1, 2902.1.
2. There are 160 parking spaces provided on the combined parking lots for this project. Please provide six (6) accessible parking spaces per Table 1106.1.
3. Specify the running slope of the modified concrete ramp on the south side of the building as well as the clear width, maximum rise and edge protection in accordance with A117.1-09 section 405.
4. Provide detail drawings of the handrail serving the modified concrete ramp (as referenced in comment 3) including extension beyond bottom of ramp per A117.1-09 section 505.
5. Specify the special inspector assigned to field welding that is currently certified for performing such inspections, 1704.2.
6. Clarify the width of the new opening through the existing north wall to the patio area. Sheet A1.0 calls for 18'8" and the structural design indicates 18', 107.2.1.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov