Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM03367
Parcel: 132130720

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03367
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/04/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify how the ventilation rates for each room were chosen (i.e. what description from Table 403.3 was each room based upon?). What is the zone air distribution effectiveness (Ez) for RTU-5, 0.8? If the ventilation calculations are not to be put on the drawings, identify the calculations and add the registrant's seal. [Initial comment: Provide calculations demonstrating adequate ventilation for the vision center. Reference: Section 403.2, IMC 2012.]
06/04/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/04/2015 ROBERT SHERRY WATER REVIEW Completed
06/05/2015 MARTIN BROWN FIRE REVIEW Approved