Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM03367
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/04/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify how the ventilation rates for each room were chosen (i.e. what description from Table 403.3 was each room based upon?). What is the zone air distribution effectiveness (Ez) for RTU-5, 0.8? If the ventilation calculations are not to be put on the drawings, identify the calculations and add the registrant's seal. [Initial comment: Provide calculations demonstrating adequate ventilation for the vision center. Reference: Section 403.2, IMC 2012.] |
| 06/04/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/04/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/05/2015 | MARTIN BROWN | FIRE | REVIEW | Approved |