Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM03367
Parcel: 132130720

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM03367
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2015 STEVE SHIELDS ZONING REVIEW Approved
05/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations demonstrating adequate ventilation for the vision center. Reference: Section 403.2, IMC 2012.
05/20/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/20/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the existing water meter and the associated backflow preventer. Will the size of the water meter be changed as a result of this activity?
05/20/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CVR; BUILDING CODE SUMMARY: ADD THE SF OF THIS TENANT SPACE ON THE DRAWING.
2. SHEET VC1; FLOOR PLAN 1: THE PLAN INDICATES WALL NUMBERS (A3, B6, C3, AND C6) THAT ARE NOT INDICATED IN THE PARTITION TYPES SCHEDULE ON THIS SHEET. PLEASE CLARIFY.
3. SHEET VC1; DETAIL 6: THE BRACING INDICATED IS REQUIRED TO MEET THE IBC SECTION 1607.14, UNLESS THE STUD WALL IS DESIGNED TO RESIST THOSE HORIZONTAL LOADS. EXTEND THIS DETAIL TO INDICATE HOW THE BRACING IS CONNECTED TO THE ROOF ABOVE, AND INDICATE THE SIZE AND QUANTITY OF CONNECTORS.
4. SHEETS VC2 AND MVC1: ARE THERE ANY NEW MECHANICAL LOADS BEING ADDED TO THE EXISTING STRUCTURE? PLEASE VERIFY (IF NEW LOADS, PROVIDE STRUCTURAL CALCULATIONS INDICATING THE EXISTING STRUCTURE CAN SUPPORT THE NEW LOADS.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/20/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/20/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify how the proposeed connection of tepid water for the sinks will limit the distance from the hot water source to less than fifty-feet. Reference: Section 607.2, IPC 2012.
05/20/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/21/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change resubmit after building comments are completed
06/04/2015 AROMERO4 WWM REVIEW Completed