Permit Number: T15CM02532
Parcel: 10825287A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM02532
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2015 STEVE SHIELDS ZONING REVIEW Approved
04/15/2015 LOREN MAKUS ENGINEERING REVIEW Approved
04/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/16/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Section C101.4.3, IECC 2012 requires relocated HVAC equipment to meet the current energy code. Include the relocated A/C unit in the mechanical compliance analysis.
04/16/2015 MARTIN BROWN FIRE REVIEW Approved
04/16/2015 ROBERT SHERRY WATER REVIEW Completed
04/16/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/16/2015 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
04/24/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET D1 (SECOND FLOOR PLAN); FLOOR PLAN KEY NOTES: NOTE D15.1 INDICATES TO REMOVE A MOP SINK. IS THIS TO BE REPLACED (IS IT REQUIRED BY THE IBC)?
2. SHEET A1 (FIRST FLOOR PLAN); SHEET S1.0 (FLOOR FRAMING PLAN): PLEASE COORDINATE THE ARCHITECTURAL AND STRUCTURAL PLANS (NUMBER OF COLUMNS, LOCATION OF COLUMNS).
3. SHEET S2.0; SECTION A: IS THE SIZE OF THE NEW TUBE ON THE BOTTOM OF THE EXISTING JOIST INDICATED ON THE DRAWINGS? PLEASE VERIFY.
4. STRUCTURAL CALCULATIONS: WAS THE WEIGHT OF THE NEW STEEL PLATES IN THE WALLS AND ON THE FLOOR ADDED TO THE LOADS SUPPORTED BY THE NEW FLOOR BEAMS? PLEASE VERIFY.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/24/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed