Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM02092
Parcel: 113010020

Address:
1802 E ROGER RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T15CM02092
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2015 MARTIN BROWN FIRE REVIEW Reqs Change Electrolyte is a hazardous material regulated by the fire code.
Please provide number of batteries, amount of electrolyte per battery, and total quantity of electrolyte in building. Refer to the 2012 International Fire Code, Chapter 50, for maximum allowable quantities.
04/10/2015 CPIERCE1 COMMUNICATIONS REVIEW Completed per Thomas Jefferson
04/21/2015 MICHAEL ST. PAUL ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T15CM02092
1802 East Roger
Cell tower


TRANSMITTAL: April 21, 2015


COMMENTS: the following comments are relative to an application for a Special Exception relative to cell tower antenna modifications.

The Special Exception is SE-15-01 (T15SE00001) for AT&T at 1802 East Roger in the MH-1 zone.

This cell tower is in the right-of-way (ROW). A right-of-way permit is required. Coordinate all the drawing and documents with the above address and apply for a ROW permit with Permits and Codes in the Transportation Department. Transportation is on the fifth (5th)) floor. Ask for Richard Leigh (520-791-5100).

Also provide the note "Paint antennas and appurtenances to match the existing color scheme" on the elevation plans.

Once the ROW permit is acquired and the note is added to the elevation drawing, the plans can be approved.
04/24/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/01/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2015 KROBLES1 OUT TO CUSTOMER Completed