Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM01732
Parcel: 11619226D

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM01732
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 440 W. Pasep Redondo - Building Plan
T15CM01732
Building Plan (2nd Review)

TRANSMITTAL DATE: May 5, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans cannot be approved until the development package, DP15-0036, has been approved.

3. Based on the drawing index shown on sheet 1 the drawings are not in the correct order.

4. The development package sheets provided in the building plans will either need to be the approved development package sheets or marked as reference only prior to approval of the building set.

5. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/05/2015 JASON GREEN ENGINEERING REVIEW Reqs Change Will stamp the building plan approved upon approval of the DP Package. JG
05/07/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/07/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/07/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/28/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change The following comments have not been sufficiently addressed from the previous review:

1. SHEET 0.2; LEGEND: THE FIRST ITEM LISTED IS A DRAFT CURTAIN. DO WE HAVE A DRAFT CURTAIN IN THIS PROJECT? PLEASE VERIFY.
Note: Without a draft curtain the open stairway on the southwest corner of the building will not be permitted to be open between the floors per 1009.3.

2. SHEET 0.2; PLANS 1, 2, AND 3: FOR EACH FLOOR, PLEASE DEFINE THE AREAS DENOTED AS B, A-3, AND S-2, AND INDICATE AN OCCUPANT LOAD AT EACH OF THOSE AREAS.
Note: The open office areas on floors 1 and 2 must have a minimum occupant load relative to the aggregate floor area per 1004.1.2.

3. SHEET 0.2; FLOOR PLAN 3: TABLE 1021.2(2) INDICATES THE THIRD STORY MUST HAVE MORE THAN ONE EXIT. THE THIRD FLOOR TENANT AREA HAS ONLY ONE EXIT (THE EXIT THROUGH THE SHELL SPACE IS NOT ALLOWED PER SECTION 1014). IF ACCESS TO EXIT 2 IS PROVIDED (CORRIDOR), INDICATE THE ALLOWED AND ACTUAL TRAVEL DISTANCE ON THE PLAN.
Note: An open shell building or area does not have an occupancy classification and therefore can not be accessory to another occupancy. Further, the definition of corridor is "An enclosed exit access component that defines and provides a path of egress travel." The enclosed corridor is required although it does not need to be fire-rated in this case.

9. SHEET 1.1; FLOOR PLAN: PER SECTION 1018.6, THE CORRIDOR MUST BE CONTINUOUS FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE INTERRUPTED BY INTERVENING ROOMS. CORRIDOR 105 (BETWEEN THE WAREHOUSE AND THE OPEN OFFICE) DOES NOT APPEAR TO MEET THAT REQUIREMENT. PLEASE VERIFY.
Note: See note associated with comment #3.

16. SHEET 1.1; WALL TYPES: PLEASE INDICATE ON WALL G THE GYPSUM BOARD ON BOTH SIDES OF THE STUD WALL MUST EXTEND CONTINUOUSLY TO THE ROOF DECK PER SECTION 707.5.
Note: Please include specification for the wall covering on each side of the wall for this notation.

21. SHEET 1.9; ELEVATIONS: SEVERAL ELEVATIONS INDICATE KEYNOTES 13 AND 14. PLEASE PROVIDE THOSE NOTES ON THE PLAN.
Note: It appears that the numbering for these two items has been transposed.

23. SHEET 3; DEVELOPMENT PACKAGE: PLEASE PROVIDE THE DISTANCE FROM THE NEW BUILDING TO THE EXISTING PROPERTY LINE ALONG THE NORTH WALL (IN ADDITION TO THE 11' DIMENSION SHOWN).
Note: A minimum distance of ten (10) feet must be maintained from all property lines unless alternate provisions of sections 602 are addressed. Please provide distances from each property line.

25. SHEET 3.0; STANDARD STRUCTURAL NOTES (GENERAL): NOTE 2G INDICATES A GEOTECHNICAL REPORT WAS USED. PLEASE PROVIDE FOR REVIEW.
Note: Sheet 3.0 was not provided with this review. Other missing sheets include: 3.2, 5.2, 5.5, 5.7, 15.8. The sheet index on the cover has the following sheets mislabeled: E5.2, E5.3

29. SHEET 5.2 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 11): BEAM B12 IN THE CALCULATIONS REQUIRES A W18X35, BUT A BEAM DENOTED AS B12 SIM IN THE CALCULATIONS INDICATES A W12X26 ON THE FRAMING PLAN (ON GRID E). PLEASE CLARIFY.
Note: See note associated with comment #25.

30. SHEET 5.2 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 16): BEAM B9 IN THE CALCULATIONS REQUIRES A W16X26, BUT THE FRAMING PLAN (ON GRID B) INDICATES A W12X30. PLEASE CLARIFY.
Note: See note associated with comment #25.

31. SHEET 5.2 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 11): TWO BEAMS MARKED B3 IN THE CALCULATIONS REQUIRE A W21X44. ON THE FRAMING PLAN (ON GRID E), ONE BEAM IS DENOTED AS A W21X44, AND ONE BEAM AS A W12X45. PLEASE CLARIFY.
Note: See note associated with comment #25.

32. SHEET 5.2 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 11): TWO BEAMS MARKED B1 IN THE CALCULATIONS REQUIRE A W18X35 OR A W18X40. ON THE FRAMING PLAN (ON GRID B), ONE BEAM IS DENOTED AS A W18X40, AND ONE BEAM AS A W12X40 (ANOTHER BEAM ON GRID E IS DENOTED AS A W12X40). PLEASE CLARIFY.
Note: See note associated with comment #25.

37. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/01/2015 AROMERO4 OUT TO CUSTOMER Completed