Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01486
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/18/2015 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Need electrical plans for reference of smoke alarms, fa, etc. Need to know how FSD are activated per the IBC |
03/20/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | There is not sufficient information to properly review the exiting for this project: a. Is the most northerly stair exit an open stair exit? b. Does the same stair exit on top of the building to the east? c. Where is the exit to the right of way. 2. Please provide the exit code analysis for exiting at the elevator lobby including all new and existing partitioning fire ratings. 3. Please provide a total building exit analysis as per the 2012 IBC, Chapter 34, Sections 1009, 1022 and 1026. 4. Are all the 10 floors being changed from "B" to "R2"? 5. Please provide a site plan showing all exiting to right of way. END OF REVIEW |
03/20/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
03/20/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter (see two locations). Reference: Section 406.2, IPC 2012. 2. The Laing "Autocirc" system specified for the P-5 fixtures appears to comply with the intent of Section 607.2, IPC 2012 in that it recirculates hot water to reduce the time required to obtain hot water at the fixtures even though it does appear to be prohibited by Section 604.2, IPC 2012. Provide an appeal to the building official to justify the use of this system. 3. Provide insulation for any recirculating hot water systems. Reference: Section C404.5, IECC, 2012. |
03/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Two of the three dryer exhaust ducts appear to have an equivalent length greater than 35-feet. If the dryer manufacturer allows the 35-foot length to be exceeded, show the make and model of the proposed dryer on the plans and provide a copy of the manufacturer's installation instructions. Reference: Section 504.6.4.2, IMC 2012. 2. Provide signage indicating the total equivalent length for each of the concealed dryer exhaust ducts. Reference: Section 504.6.5, IMC 2012. 3. Positively pressurized exhaust ducts from areas allowed to have up to 10% recirculation per Section 403.2.1 item 4 (e.g. bathrooms), may not pass through a plenum unless the duct is sealed in accordance with Section 603.9, IMC 2012. Reference: Section 601.4, IMC 2012. 4. Positively pressurized exhaust ducts from areas not allowed to have up to 10% recirculation per Section 403.2.1 item 3 (e.g. kitchens), may not pass through a plenum. Reference: Section 601.4, IMC 2012. |
03/24/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Approval subject to subsequent review due to possible structural or mechanical changes. |
03/31/2015 | AROMERO4 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |