Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM01347
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/02/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/02/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/02/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/02/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/02/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/02/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
| 03/02/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/02/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/02/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/02/2015 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/11/2015 | AROMERO4 | APPROVAL SHELF | Completed |
| 03/11/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 03/11/2015 | AROMERO4 | REJECT SHELF | Completed |