Permit Number: T15CM01104
Parcel: 13413057X

Address:
35 S PANTANO RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM01104
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2015 KEN BROUILLETTE FIRE REVIEW Approved -
03/13/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET PV1.1
1. At details 2 and 4, please analyize the vertical movement of the high end of the canopy to insure clearance from the building gutters and fascia overhangs.
2. Roof area calculates to be 8,934 s.f as opposed to that shown on sheet G000 of 8,092. Please reconcile.
03/16/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/16/2015 ROBERT SHERRY WATER REVIEW Passed
03/16/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/18/2015 LOREN MAKUS ENGINEERING REVIEW Denied DP must be approved first.
03/20/2015 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Surf Thru Car Wash
T15CM01103 & T15CM01104
Building Plan (1st Review)

TRANSMITTAL DATE: March 20, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans cannot be approved until the development package, DP14-0191, has been approved.

3. It does not appear that the proposed PV canopies meet the requirements of UDC Section 7.4.6.F.2.a.(1).

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2015 KROBLES1 OUT TO CUSTOMER Completed