Permit Number: T15CM00727
Parcel: 14043013B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00727
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 8: SHEET A3.1; BUILDING SECTION DD: AN ENLARGED SECTION ON THE RIGHT SIDE REFERENCES A/A1.0. PLEASE REVISE THE REFERENCE.
02/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Information on the features of the thermostat was not found. [Initial comment: Clarify the nature of the thermostatic control, i.e. is it programmable with the features required by Section C403.2.4.2, IFGC, 2012.]
2. Keynote #15 on sheet still calls for a 2-degree Fahrenheit deadband. [Initial comment: Provide justification for having thermostat set points with less than a 5-degree Fahrenheit deadband. Reference: Section C403.2.4.2, IECC 2012.]
02/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved