Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00727
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/20/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 8: SHEET A3.1; BUILDING SECTION DD: AN ENLARGED SECTION ON THE RIGHT SIDE REFERENCES A/A1.0. PLEASE REVISE THE REFERENCE. |
| 02/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Information on the features of the thermostat was not found. [Initial comment: Clarify the nature of the thermostatic control, i.e. is it programmable with the features required by Section C403.2.4.2, IFGC, 2012.] 2. Keynote #15 on sheet still calls for a 2-degree Fahrenheit deadband. [Initial comment: Provide justification for having thermostat set points with less than a 5-degree Fahrenheit deadband. Reference: Section C403.2.4.2, IECC 2012.] |
| 02/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |