Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM08772
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2015 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera Principal Planner PROJECT: T14CM08772 and T14CM08764 20 E Congress Street T.I. - CMU ANNEX TRANSMITTAL DATE: January 5, 2015 DUE DATE: January 23, 2015 COMMENTS: 01. Zoning has reviewed the T.I. plans for the CMU ANNEX but cannot approve them at this time. While T.I. plans in the downtown are generally an over the counter review, these T.I. plans appear to include exterior façade work. The exterior façade work must be reviewed by Frank Dillon or Michael Taku for compliance with the HPZ and or DRB approved plans and if applicable any conditions of said approvals. 02. Add the DRB and HPZ case numbers on the plan sheets in the lower right corner of all plan sheets. The set of T.I. plans do not include typical cover sheet where the HPZ and DRB case numbers are listed as a general note along with the approval date and any conditions of approval. 03. Once the Frank or Michael have stamped and signed off the T.I. Plans zoning will approve and stamp the T.I. plans sheets as well. Ensure that all reviewers comments have been addressed. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. |
| 01/05/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Waiting for revisions based on Building Code Official review. |
| 01/12/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET AI0.0; EXIT DIAGRAMS: THE MEASUREMENT FOR THE EXIT ACCESS TRAVEL DISTANCE DOES NOT FOLLOW THE IBC SECTION 1016.3. REVISE THE MEASUREMENT ON THE DIAGRAM, AND VERIFY THE REQUIREMENTS OF TABLE 1021.2(2) ARE MET. THIS MEASUREMENT COULD CHANGE ONCE A TENANT HAS OCCUPIED THE SPACE. 2. SHEET AI2.0; BASEMENT PLAN: A KEYNOTE 2 LOCATED IN THE ELEVATOR IS NOT CORRECT IN THIS LOCATION. VERIFY. 3. SHEET AI7.0; TYPICAL WALL DETAILS W.TI-1 AND W.TI-1.6: THE DETAILS INDICATE TO 'SEE STRUCTURAL'. REVISE AND PROVIDE INFORMATION ON THE DETAILS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/13/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/14/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/22/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Approval subject to subsequent review, due to potential egress changes. D Santa Cruz, Elect, Plans Examiner 520-837-9077 |