Permit Number: T14CM08772
Parcel: 117120860

Address:
20 E CONGRESS ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08772
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2015 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
Principal Planner

PROJECT: T14CM08772 and T14CM08764
20 E Congress Street
T.I. - CMU ANNEX

TRANSMITTAL DATE: January 5, 2015

DUE DATE: January 23, 2015

COMMENTS:

01. Zoning has reviewed the T.I. plans for the CMU ANNEX but cannot approve them at this time. While T.I. plans in the downtown are generally an over the counter review, these T.I. plans appear to include exterior façade work. The exterior façade work must be reviewed by Frank Dillon or Michael Taku for compliance with the HPZ and or DRB approved plans and if applicable any conditions of said approvals.

02. Add the DRB and HPZ case numbers on the plan sheets in the lower right corner of all plan sheets. The set of T.I. plans do not include typical cover sheet where the HPZ and DRB case numbers are listed as a general note along with the approval date and any conditions of approval.

03. Once the Frank or Michael have stamped and signed off the T.I. Plans zoning will approve and stamp the T.I. plans sheets as well. Ensure that all reviewers comments have been addressed.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
01/05/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change Waiting for revisions based on Building Code Official review.
01/12/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET AI0.0; EXIT DIAGRAMS: THE MEASUREMENT FOR THE EXIT ACCESS TRAVEL DISTANCE DOES NOT FOLLOW THE IBC SECTION 1016.3. REVISE THE MEASUREMENT ON THE DIAGRAM, AND VERIFY THE REQUIREMENTS OF TABLE 1021.2(2) ARE MET. THIS MEASUREMENT COULD CHANGE ONCE A TENANT HAS OCCUPIED THE SPACE.
2. SHEET AI2.0; BASEMENT PLAN: A KEYNOTE 2 LOCATED IN THE ELEVATOR IS NOT CORRECT IN THIS LOCATION. VERIFY.
3. SHEET AI7.0; TYPICAL WALL DETAILS W.TI-1 AND W.TI-1.6: THE DETAILS INDICATE TO 'SEE STRUCTURAL'. REVISE AND PROVIDE INFORMATION ON THE DETAILS.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/13/2015 ROBERT SHERRY WATER REVIEW Completed
01/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/22/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied Approval subject to subsequent review, due to potential egress changes.
D Santa Cruz, Elect, Plans Examiner
520-837-9077