Permit Number: T14CM08764
Parcel: 117120860

Address:
20 E CONGRESS ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM08764
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 1: UPON FINAL APPROVAL OF THE BUILDING SHELL PERMIT (T14CM06042), ADDITIONAL COMMENTS MAY BE ADDED IN SUBSEQUENT REVIEWS.
2. PREVIOUS COMMENT 2: PLEASE PLACE SHEET AI0.0 IMMEDIATELY AFTER THE COVER SHEET.
3. PREVIOUS COMMENT 6: PLEASE INCLUDE ON THE DRAWINGS AND SPECIFICATIONS (AS REQUIRED) WHAT PARAMETERS THE NFPA SPECIFICALLY REQUIRES CONCERNING THE DRAFT CURTAINS AND CLOSELY SPACED SPRINKLERS AT THE OPEN, INTERIOR STAIR.
4. SHEETS AI0.0 AND AI2.3 (NOTE 15); PLANS: THE EXTERIOR AREA OF ASSISTED RESCUE SHOULD BE NOTED AS SUCH, NOT AN AREA OF REFUGE. PLEASE REVISE.
5. PREVIOUS COMMENT 25: PLEASE PROVIDE DETAILS ON THE DRAWINGS AT THE FIRST AND SECOND FLOOR CEILINGS AT THE DRAFT CURTAIN FOR THE OPEN, INTERIOR STAIR TO VERIFY THE REQUIREMENTS OF THE IBC SECTION 1009.3 AND THE NFPA SECTION 8..15.4.2 ARE MET.
6. GENERAL: SHEET AI5.2 WAS NOT INCLUDED IN BOTH SUBMITTED SETS. PLEASE PROVIDE.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/10/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/13/2015 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
Principal Planner

PROJECT: T14CM08772 and T14CM08764
20 E Congress Street
T.I. - CMU ANNEX

TRANSMITTAL DATE: March 13, 2015

DUE DATE: March 24, 2015
COMMENTS: Provide a response comment memo explain how the zoning comments have been addressed.

01. Zoning has reviewed the T.I. plans for the CMU ANNEX but cannot approve them at this time. While T.I. plans in the downtown are generally an over the counter review, these T.I. plans appear to include exterior façade work. The exterior façade work must be reviewed by Frank Dillon or Michael Taku for compliance with the HPZ and or DRB approved plans and if applicable any conditions of said approvals.
Once all the building disciplines have approved the building plans, the plans must be taken to Zoning Administration staff for their stamp and signature. Once ZA Staff has signed off on the building plans the Zoning Review Section will approve the building plans.

02. Add the DRB and HPZ case numbers on the plan sheets in the lower right corner of all plan sheets. The set of T.I. plans do not include typical cover sheet where the HPZ and DRB case numbers are listed as a general note along with the approval date and any conditions of approval.

03. Once the Frank or Michael have stamped and signed off the T.I. Plans zoning will approve and stamp the T.I. plans sheets as well. Ensure that all reviewers' comments have been addressed.
If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
03/17/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/18/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. PLEASE INCLUDE ON THE DRAWINGS AND SPECIFICATIONS (AS REQUIRED) WHAT PARAMETERS THE NFPA SPECIFICALLY REQUIRES CONCERNING THE DRAFT CURTAINS AND CLOSELY SPACED SPRINKLERS AT THE OPEN, INTERIOR STAIR.
2. THE EXTERIOR AREA OF ASSISTED RESCUE SHOULD BE NOTED AS SUCH, NOT AN AREA OF REFUGE. PLEASE REVISE.
3. PLEASE PROVIDE DETAILS ON THE DRAWINGS AT THE FIRST AND SECOND FLOOR CEILINGS AT THE DRAFT CURTAIN FOR THE OPEN, INTERIOR STAIR TO VERIFY THE REQUIREMENTS OF THE IFC SECTION 1009.3 AND THE NFPA 13.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2015 KROBLES1 OUT TO CUSTOMER Completed