Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM08764
Parcel: 117120860

Address:
20 E CONGRESS ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08764
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2015 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
Principal Planner

PROJECT: T14CM08772 and T14CM08764
20 E Congress Street
T.I. - CMU ANNEX

TRANSMITTAL DATE: January 5, 2015

DUE DATE: January 23, 2015

COMMENTS:

01. Zoning has reviewed the T.I. plans for the CMU ANNEX but cannot approve them at this time. While T.I. plans in the downtown are generally an over the counter review, these T.I. plans appear to include exterior façade work. The exterior façade work must be reviewed by Frank Dillon or Michael Taku for compliance with the HPZ and or DRB approved plans and if applicable any conditions of said approvals.

02. Add the DRB and HPZ case numbers on the plan sheets in the lower right corner of all plan sheets. The set of T.I. plans do not include typical cover sheet where the HPZ and DRB case numbers are listed as a general note along with the approval date and any conditions of approval.

03. Once the Frank or Michael have stamped and signed off the T.I. Plans zoning will approve and stamp the T.I. plans sheets as well. Ensure that all reviewers comments have been addressed.


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
01/05/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change Waiting for revisions based on Building Code Official review.
01/08/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THIS TENANT IMPROVEMENT IS CURSORY IN NATURE ONLY. THERE ARE SEVERAL EGRESS AND EXITING ISSUES THAT NEED TO BE RESOLVED BEFORE THIS TENANT IMPROVEMENT CAN BE FULLY REVIEWED. THOSE ISSUES WILL BE PRESENTED IN THIS REVIEW, AND A FULL REVIEW FOR THIS TENANT IMPROVEMENT WILL FOLLOW THE APPROVAL OF THE SHELL BUILDING DRAWINGS (T14CM06042). ADDITIONAL COMMENTS MAY BE ADDED IN SUBSEQUENT REVIEWS FOLLOWING THE SHELL BUILDING APPROVAL.
2. SHEET AI0.0: THIS SHEET SHOULD BE PLACED IMMEDIATELY AFTER THE COVER SHEET.
3. SHEET AI0.0; EXIT DIAGRAMS (SECOND AND THIRD FLOORS): PROVIDE ON THE PLANS AN EXIT ACCESS TRAVEL DISTANCE AND PATH. VERIFY THE REQUIREMENTS OF THE IBC SECTION 1016 ARE MET.
4. SHEET AI0.0; EXIT DIAGRAMS: ALTHOUGH THIS PERMIT INCLUDES ONLY THE SECOND AND THIRD FLOORS, THE MEASUREMENT FOR THE EXIT ACCESS TRAVEL DISTANCE IN THE BASEMENT DOES NOT FOLLOW THE IBC SECTION 1016.3. FOLLOW THE REQUIREMENTS OF THAT SECTION FOR THE SECOND AND THIRD FLOOR EXIT ACCESS TRAVEL DISTANCE MEASUREMENTS.
5. SHEET AI0.0; GENERAL BUILDING HEIGHTS AND AREAS: REFERENCE IS MADE TO TABLE 406.3.5. REVISE THIS REFERENCE NUMBER.
6. SHEET AI0.0; FIRE PROTECTION SYSTEMS: AT THE OPEN STAIR NOTES, ADD VERBIAGE THAT THE OPENING SHALL HAVE DRAFT CURTAINS AND CLOSELY SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13 (AS NOTED IN EXCEPTIONS 3 AND 4).
7. SHEET AI0.0: INDICATE ON THIS SHEET THAT THE INTERIOR EXIT STAIRWAY SHALL BE ENCLOSED PER THE IBC SECTION 1009.2.2, AND THAT THE ENCLOSURE SHALL BE CONSTRUCTED PER THE IBC SECTION 1022.2 FOR A FIRE BARRIER PER SECTION 707 AND HAVE A RATING NOT LESS THAN TWO HOURS.
8. SHEET AI0.0; BUILDING CODES: ON THE DRAWINGS, PROVIDE AN ANALYSIS OF ALL REQUIRED EXIT DOOR AND STAIR WIDTHS.
9. SHEET AI0.0; EXIT DIAGRAMS (FIRE PROTECTION): ADDRESS ON THE DRAWINGS THE NEED TO FIRE RATE THE ROOF OF THE EXISTING BUILDING TO THE NORTH DUE TO THE EXITING OF THE THIRD FLOOR OCCUPANTS ONTO THAT ROOF.
10. SHEET AI2.2; SECOND FLOOR PLAN: IF A NO-BUILD EASEMENT IS APPROVED ON THE WEST SIDE OF THE BUILDING, THE BALCONIES AT THE SECOND AND THIRD FLOORS, AND THE WINDOW AWNINGS INDIATED IN THREE LOCATIONS MUST BE REMOVED.
11. SHEETS AI2.2 AND AI2.3; FLOOR PLAN: ADDRESS ON THE DRAWINGS THE IBC REQUIREMENTS FOR AREAS OF REFUGE (SECTION 1007.6) AND EXTERIOR AREAS FOR ASSISTED RESCUE (SECTION 1007.7) AT ACCESSIBLE MEANS OF EGRESS. INCLUDE COMMUNICATION AND SIGNAGE REQUIREMENTS, ALONG WITH FIRE SEPARATIONS (SECTIONS 1007.7.4 AND 1026.6). THIS WILL INCLUDE THE INTERIOR ACCESSIBLE EXIT STAIR AND THE EXTERIOR ACCESSIBLE EXIT STAIR.
12. SHEET AI2.2; KEYNOTES: NOTE 26 WAS NOT LOCATED ON THIS SHEET. VERIFY.
13. SHEET AI2.2 (FLOOR PLAN); SECTION 1/AI5.2: THE SECTION INDICATES THE THIRD FLOOR BALCONY AND THE SECOND FLOOR WINDOW AWNING, BUT THE SECTION IS NOT CUT AT THAT LOCATION. VERIFY.
14. SHEETS AI2.2 AND AI2.3; FLOOR PLAN: PROVIDE DETAILS, SECTIONS, AND SPECIFICATIONS FOR THE NEW INTERIOR STAIR ON THE EAST SIDE OF THE BUILDING. IF THIS WAS PART OF THE SHELL DRAWINGS, PROVIDE A NOTE ON THE PLANS.
15. SHEET AI2.2; PLAN A (ADA DIMENSIONS): THE CLEAR DISTANCE BETWEEN PARTITIONS AT THE URINAL IS REQUIRED TO BE 36" MINIMUM PER THE ICC/ANSI FIGURE 305.7(a). VERIFY THE 3'-0" SHOWN ON THE PLAN IS CLEAR DISTANCE.
16. SHEETS AI2.2 AND AI2.3; FLOOR PLAN: ARE THE BALCONIES AND WINDOW AWNINGS NEW OR EXISTING? IF NEW, STRUCTURAL CALCULATIONS AND DETAILS ARE REQUIRED. IF THESE WERE PART OF THE SHELL DRAWINGS, PROVIDE A NOTE ON THE PLANS.
17. SHEET AI2.3; FLOOR PLAN: PROVIDE A RAMP AND DETAIL AT THE NORTH EXIT ONTO THE ROOF OF THE ADJACENT BUILDING. THERE IS NO INDICATION OF AN ELEVATION CHANGE FROM THE THIRD FLOOR TO THE ROOF ON THE DRAWINGS (1/AI5.0 AND 1/AI5.1).
18. SHEET AI2.3; KEYNOTES: NOTES 2, 3, AND 5 WERE NOT LOCATED ON THE PLAN. VERIFY.
19. SHEET AI3.2; KEYNOTES: NOTE 4 INDICATES A NEW STEEL STAIR. PROVIDE CALCULATIONS FOR THE STAIR AND IT'S FOUNDATION. IF THIS WAS A PART OF THE SHELL DRAWINGS, PROVIDE A NOTE ON THE PLANS.
20. SHEET AI3.2; KEYNOTES: NOTE 6 REFERENCES THE 2013 IBC. REVISE.
21. SHEET AI3.3; KEYNOTES: NOTE 2 REFERENCES THE 2013 IBC. REVISE.
22. SHEET AI3.3; KEYNOTES: NOTE 5 WAS NOT LOCATED ON THE PLAN. VERIFY.
23. SHEET AI5.0; KEYNOTES: NOTE 18 REFERENCES SHEET A6.0 FOR A NEW STAIR. REVISE THE REFERENCE.
24. SHEET AI5.0; KEYNOTES: NOTE 28 REFERENCES STRUCTURAL. REVISE THE REFERENCE.
25. SHEET AI5.0; KEYNOTES: NOTE 19 INDICATES TO SEE A DETAIL FOR THE DRAFT CURTAIN. PROVIDE THE SPECIFIC DETAIL NUMBER.
26. SHEET AI5.0; KEYNOTES: THERE ARE MANY NOTES NOT LOCATED ON THE SECTION. VERIFY.
27. SHEET AI7.0; TYPICAL INTERIOR WALL DETAIL: AT THE TOP OF THE WALL, PROVIDE THE DIAGONAL BRACING SIZE AND CONNECTION TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE. USE DETAILS AS REQUIRED.
28. SHEET AI7.0; TYPICAL WALL DETAILS W.TI-1 AND W.TI-3: THESE DETAILS INDICATE TO 'SEE STRUCTURAL'. REVISE AND PROVIDE INFORMATION ON THE DETAILS.
29. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/13/2015 ROBERT SHERRY WATER REVIEW Completed
01/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the HVAC unit numbers used in the cooling/heating load calculations with the unit numbers shown on the drawings.
01/22/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied Approval subject to subsequent review, due to potential egress changes.
D Santa Cruz, Elect.Plans Examiner
520-837-9077