Permit Number: T14CM07150
Parcel: 11107191B

Address:
3206 E GLENN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T14CM07150
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2015 CPIERCE1 ENGINEERING REVIEW Needs Review
04/16/2015 CPIERCE1 BUILDING-RESIDENTIAL REVIEW Needs Review
10/24/2014 STEVE SHIELDS ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Steve Shields, Lead Planner

PROJECT:
T14CM07150
3206 E. Glenn Street
Permit existing 2-Story Addition w/ deck area


TRANSMITTAL: October 24, 2014


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 23'-6" at the south end of the addition the required perimeter yard setback from the addition to the west property line is 15'-8", proposed is 5'-2".

Based on a wall height of 20'-6" at the north end of the addition the required perimeter yard setback from the addition to the west property line is 13'-8", proposed is 4'-8".

Based on a wall height of 14'-0" at the deck the required perimeter yard setback from the deck to the west property line is 9'-4", proposed is 5'-9".

See LDO-01-32 for garage addition.
10/24/2014 SSHIELD1 NPPO REVIEW Passed