Permit Number: T14CM06518
Parcel: 11706183B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM06518
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET a2.0; DEMO KEY NOTES: NOTE 7 WAS NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET a2.0; DEMO KEY NOTES: THE FLOOR PLAN REFERENCES KEYNOTE 15 IN SEVERAL LOCATIONS, BUT THERE IS NO NOTE 15 LISTED. VERIFY.
3. SHEET a3.0 (WALL TYPES); SHEET a9.2: WALL TYPE C REFERENCES DETAIL 49/a9.2. THAT DETAIL INDICATES IT WAS NOT USED. CLARIFY.
4. SHEET a3.0; GENERAL FLOOR PLAN NOTES: NOTE 18 REFERENCES SHEET a8.0 FOR BATHROOMS. IS THIS REFERENCE CORRECT? VERIFY.
5. SHEET a3.0; FLOOR PLAN/DIMENSION + FINISH FLOOR PLANS: SECTION 3/a8.0 IS CUT AT THE ENTRY AND CONTINUES THROUGH THE INTERIOR DOUBLE DOOR. AT THE INTERIOR, THE SECTION IS REFERENCED AS 3/a7.1. CLARIFY.
6. SHEET a3.0; FLOOR PLAN KEY NOTES: NOTE 60 REFERENCES THE 2007 ANSI. REVISE.
7. SHEET a3.0; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE RAMP VERBIAGE.
8. SHEET a3.0; FLOOR PLAN KEY NOTES: FINISH THE DETAIL REFERENCE IN NOTE 61.
9. SHEET a3.0; FLOOR PLAN KEY NOTES: NOTES 12, 18, 29, 31, 40, 44, 48, 58, 59, AND 63 WERE NOT LOCATED ON THE PLAN. VERIFY.
10. SHEET a4.0; GENERAL NOTES: NOTE 9 REFERENCES SHEET a5.0 FOR CEILING HEIGHTS. IS THIS CORRECT? VERIFY.
11. SHEET a4.0; GENERAL NOTES: NOTE 12 REFERENCES SHEET S2.0 FOR CEILING STRUCTURE LAYOUT. REVISE.
12. SHEET a4.0; KEY NOTES: NOTES 11, 17, 21, AND 24 WERE NOT LOCATED ON THE PLAN. VERIFY.
13. SHEET a9.1; DETAILS 27, 32, AND 38: INDICATE ON THESE DETAILS HOW THE DIAGONAL BRACING CONNECTS TO THE STRUCTURE ABOVE. INCLUDE CONNECTOR SIZE AND QUANTITY.
14. SHEET a9.2; DETAIL 51: IS THE TITLE 'WOOD WALL' PERTINENT TO THIS DETAIL? VERIFY.
15. SHEET a9.2; DETAIL 50: INDICATE ON THE DETAIL HOW THE THREADED ROD IS SUPPORTED AT THE STRUCTURE ABOVE. PROVIDE A ROD DIAMETER.
16. SHEET a9.2; DETAIL 50: PROVIDE A THICKNESS FOR THE 4X4 STEEL ANGLE FRAME AND THE 2X2 ANGLES. INDICATE A MINIMUM OF TWO FRAMES AT THE WATER HEATER SUPPORT.
17. SHEET a9.2; DETAIL 50: AT THE BLOCKING, INDICATE THE SIZE AND QUANTITY OF LAG BOLTS.
18. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/29/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
10/29/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide exhaust for cooking appliances (convection oven, induction cooker, etc.) that do not require the installation of a Type II hood. Reference: Section 507.2.2, IMC 2012.
10/30/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2014 AROMERO4 REJECT SHELF Completed