Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM06518
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET a2.0; DEMO KEY NOTES: NOTE 7 WAS NOT LOCATED ON THE PLAN. VERIFY. 2. SHEET a2.0; DEMO KEY NOTES: THE FLOOR PLAN REFERENCES KEYNOTE 15 IN SEVERAL LOCATIONS, BUT THERE IS NO NOTE 15 LISTED. VERIFY. 3. SHEET a3.0 (WALL TYPES); SHEET a9.2: WALL TYPE C REFERENCES DETAIL 49/a9.2. THAT DETAIL INDICATES IT WAS NOT USED. CLARIFY. 4. SHEET a3.0; GENERAL FLOOR PLAN NOTES: NOTE 18 REFERENCES SHEET a8.0 FOR BATHROOMS. IS THIS REFERENCE CORRECT? VERIFY. 5. SHEET a3.0; FLOOR PLAN/DIMENSION + FINISH FLOOR PLANS: SECTION 3/a8.0 IS CUT AT THE ENTRY AND CONTINUES THROUGH THE INTERIOR DOUBLE DOOR. AT THE INTERIOR, THE SECTION IS REFERENCED AS 3/a7.1. CLARIFY. 6. SHEET a3.0; FLOOR PLAN KEY NOTES: NOTE 60 REFERENCES THE 2007 ANSI. REVISE. 7. SHEET a3.0; FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE RAMP VERBIAGE. 8. SHEET a3.0; FLOOR PLAN KEY NOTES: FINISH THE DETAIL REFERENCE IN NOTE 61. 9. SHEET a3.0; FLOOR PLAN KEY NOTES: NOTES 12, 18, 29, 31, 40, 44, 48, 58, 59, AND 63 WERE NOT LOCATED ON THE PLAN. VERIFY. 10. SHEET a4.0; GENERAL NOTES: NOTE 9 REFERENCES SHEET a5.0 FOR CEILING HEIGHTS. IS THIS CORRECT? VERIFY. 11. SHEET a4.0; GENERAL NOTES: NOTE 12 REFERENCES SHEET S2.0 FOR CEILING STRUCTURE LAYOUT. REVISE. 12. SHEET a4.0; KEY NOTES: NOTES 11, 17, 21, AND 24 WERE NOT LOCATED ON THE PLAN. VERIFY. 13. SHEET a9.1; DETAILS 27, 32, AND 38: INDICATE ON THESE DETAILS HOW THE DIAGONAL BRACING CONNECTS TO THE STRUCTURE ABOVE. INCLUDE CONNECTOR SIZE AND QUANTITY. 14. SHEET a9.2; DETAIL 51: IS THE TITLE 'WOOD WALL' PERTINENT TO THIS DETAIL? VERIFY. 15. SHEET a9.2; DETAIL 50: INDICATE ON THE DETAIL HOW THE THREADED ROD IS SUPPORTED AT THE STRUCTURE ABOVE. PROVIDE A ROD DIAMETER. 16. SHEET a9.2; DETAIL 50: PROVIDE A THICKNESS FOR THE 4X4 STEEL ANGLE FRAME AND THE 2X2 ANGLES. INDICATE A MINIMUM OF TWO FRAMES AT THE WATER HEATER SUPPORT. 17. SHEET a9.2; DETAIL 50: AT THE BLOCKING, INDICATE THE SIZE AND QUANTITY OF LAG BOLTS. 18. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/29/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012. |
| 10/29/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide exhaust for cooking appliances (convection oven, induction cooker, etc.) that do not require the installation of a Type II hood. Reference: Section 507.2.2, IMC 2012. |
| 10/30/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/10/2014 | AROMERO4 | REJECT SHELF | Completed |