Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T14CM06286
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/17/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. There are nine different entries for the first floor level. Clarify the extent of each level. Reference: Section 107.2.1, IBC 2012. 2. According to the civil plans, the new rim elevation of the next upstream sanitary manhole is 2421.32'and while some portions of the first floor may be lower than or less than 12" above the manhole rim elevation, some floor areas are nearly 5-feet higher than the rim elevation of the manhole. Revise the plumbing design so that no fixtures located on floor levels that are more than 12" above the rim elevation of the manhole discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson. |
06/23/2015 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/23/2015 | AROMERO4 | APPROVAL SHELF | Completed |
06/23/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |