Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM06286
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | 1. THERE MUST BE AN APPROVED APPEAL BY THE BUILDING OFFICIAL TO ALLOW UNLIMITED FLOOR LEVELS BELOW THE THREE HOUR HORIZONTAL ASSEMBLY PER THE 2015 IBC SECTION 510.2. 2. THE MAXIMUM ALLOWABLE BUILDING HEIGHT SHALL BE REVISED ON THE DRAWINGS SO IT DOES NOT EXCEED THE LIMITS SET FORTH IN THE IBC SECTIONS 503 AND 504 FOR NON-OCCUPIED AREAS. 3. THIS CONDITIONAL PERMIT APPROVAL ALLOWS CONSTRUCTION TO BEGIN ON THE FOUNDATION ONLY. SHOULD THE QUALIFYING CONDITIONS NOT BE MET IN THE SUBSEQUENT PLAN REVIEW, THE CONTRACTOR, ARCHITECT, AND OWNER SHALL BE AT-RISK FOR WORK COMPLETED THAT MIGHT POSSIBLY BE REQUIRED TO CHANGE. |
| 05/07/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/17/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 06/17/2015 | AROMERO4 | REJECT SHELF | Completed |
| 05/12/2015 | FERNE RODRIGUEZ | APPROVAL SHELF | Approved |