Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T14CM06042
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/19/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/20/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | FROM: David Rivera Principal Planner PROJECT: T14CM06042 20 E Congress Street Facade Remodel TRANSMITTAL DATE: November 20, 2014 DUE DATE: December 03, 2014 COMMENTS: The previous Zoning review comments were not addressed. The requested information has not been added to the plans as requested and the DRB decision letter was not included in the document package. Provide a response letter and explain how the zoning review comments have been addressed. 01. Zoning cannot approve the building plans for the Façade remodel until the DRB decision letter has been issued and any conditions of the approval are incorporated into the building plans. 02. Zoning is willing to review the building plans as it pertains to the facade changes over the counter with an appointment. Be sure to include the decision letter and the stamped preliminary drawings with the next submittal. If you would like to have the plans reviewed over the counter call in advance for an appointment and I will reserve a time slot. 03. The RND number and the conditions of approval must be listed on the cover sheet of the building plans set and if applicable compliance with the conditions of approval must be demonstrated on the applicable plan sheets. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. |
11/20/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide approved appeal from the building official to use an easement for set back requirements and provide documentation of easement agreement. END OF REVIEW |
12/01/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | ENG will stamp the plan approved after the DRB has been approved. JG |
12/01/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM06042 1. Electrical floor plan: Clarify the two existing panel B entries shown on the basement plan, sheet E2.0. Either existing panel B is relocated next to panel A, or there are two labeled as B with one being removed and one remaining next to panel A? 2. Panel schedule information: Remove or clarify the total load shown on panel 2A, sheet E1.2. Ken Van Karsen PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |
12/08/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the alterations to the building envelope (the submitted COMcheck Envelope Compliance Certificate is labeled "FAILS"). Provide sufficient detail on the drawings to evaluate the energy compliance of the alterations to the building envelope. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Sections C101.4.3, C101.5, C103.2, and C303.1, International Energy Conservation Code 2012. 2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
12/08/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
12/08/2014 | ROBERT SHERRY | WATER | REVIEW | Completed |