Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; CODE REVIEW CHECKLIST: REVISE THE ACCESSIBILITY CODE TO THE 2009 EDITION.
2. SHEET A1.0; CODE REVIEW CHECKLIST (OCCUPANT LOAD AND EXITING): WHAT PORTION OF THE BUILDING IS THE RESIDENTIAL AREA (780 SF)? VERIFY.
3. SHEET A1.0; CODE REVIEW CHECKLIST (PLUMBING FIXTURE CALCULATIONS): PER THE IBC TABLE 2902.1, BUSINESS OCCUPANCIES REQUIRE ONE WATER CLOSET PER 25 PEOPLE FOR THE FIRST 50 (FOR EACH SEX). THEREFORE, 4 TOTAL WATER CLOSETS ARE REQUIRED (44 MALES, 44 FEMALES). ALTHOUGH 2 PER SEX IS INDICATED ON THE PLAN, THE VERBIAGE ONLY INDICATES 1. CLARIFY.
4. SHEET A1.0; CODE REVIEW CHECKLIST (PLUMBING FIXTURE CALCULATIONS): PER THE IBC TABLE 2902.1, BUSINESS OCCUPANCIES REQUIRE ONE LAVATORY PER 40 PEOPLE FOR THE FIRST 80 (FOR EACH SEX). THEREFORE, 4 TOTAL LAVATORIES ARE REQUIRED. ONLY 2 TOTAL ARE INDICATED ON THE FLOOR PLAN. CLARIFY.
5. SHEET A1.0 (CODE REVIEW CHECKLIST); SHEET A2.0 (FLOOR PLAN): THE CODE REVIEW CHECKLIST INDICATES 2 POINT OF USE DRINKING FOUNTAINS ARE PROVIDED. LOCATE THESE ON THE FLOOR PLAN.
6. SHEET A1.0 (DEFERRED SUBMITTALS); CODE REVIEW CHECKLIST (GENERAL BUILDING SUMMARY): THE SUMMARY INDICATES NO SPRINKLER SYSTEM, WHILE A FIRE ALARM AND SPRINKLER ARE LISTED UNDER DEFERRED SUBMITTALS. CLARIFY.
7. SHEET D1.0 (DEMOLITION PLAN); DEMOLITION PLAN KEYNOTES: IS NOTE 11 (LOCATED IN ROOM 107) CORRECT AT THIS LOCATION? VERIFY.
8. SHEET A2.0; FLOOR PLAN GENERAL NOTES: REVISE NOTE 8 TO DELETE SOME VERBIAGE.
9. SHEET A2.0; WALL TYPE NOTES: FINISH THE DETAIL REFERENCE IN NOTE 1.
10. SHEET A2.0; WALL TYPES: PROVIDE THE WALL STUD SPACING IN WALL TYPE D.
11. SHEET A2.0; FLOOR PLAN: INDICATE THE NEW WALL TYPE ADJACENT TO DOOR 119A.
12. SHEET A2.0 (FLOOR PLAN); FLOOR PLAN KEYNOTES: IS NOTE 3 (LOCATED IN ROOM 102) CORRECT AT THIS LOCATION? VERIFY.
13. SHEET A2.0 (FLOOR PLAN); FLOOR PLAN KEYNOTES: NOTE 22 INDICATES ROOMS #127 AND #128. REFERENCE THESE ROOM LOCATIONS ON THE PLAN.
14. SHEET A6.1: THIS BUILDING SECTION AND KEYNOTES ARE A REPEAT OF SHEET A6.0. THE SHEET IS NOT LISTED IN THE SHEET INDEX. CLARIFY.
15. SHEET A7.0; BREAK ROOM ELEVATION 1: MOVE THE TITLE UNDER THE ELEVATION.
16. SHEET A7.0; BREAK ROOM ELEVATION 2: PER THE IBC SECTION 1109.3, THE SINK AREA IN THE BREAK ROOM MUST BE 2'-10" ABOVE THE FINISH FLOOR FOR ACCESSIBILITY. REVISE.
17. SHEET A7.0; INTERIOR ELEVATION KEYNOTES: NOTE 8 WAS NOT LOCATED ON THE ELEVATIONS. VERIFY.
18. SHEET S2.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: INCLUDE AN ANALYSIS IN THE CALCULATIONS FOR THE NEW COLUMN LOADINGS ON THE EXISTING POST TENSIONED SLAB.
19. SHEET S2.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: INCLUDE AN ANALYSIS IN THE CALCULATIONS OF THE NEW COLUMNS C1 AS INDICATED ON THE FOUNDATION PLAN.
20. SHEET S2.1; FOUNDATION PLAN: AN INTERIOR DETAIL CUT AT THE SOUTH PORCH REFERENCES 102A. THERE IS NO 'A' OPTION ON THIS DETAIL. CLARIFY.
21. SHEET S3.1 (FRAMING PLAN); STRUCTURAL CALCULATIONS: AT THE SOUTH PORCH AREA, THERE ARE BEAMS DESIGNATED AS B6 AND B4. CLARIFY AND INCLUDE THESE BEAMS IN THE CALCULATIONS.
22. SHEET S3.1 (FRAMING PLAN); STRUCTURAL CALCULATIONS: AT THE BREAK ROOM AREA, THERE ARE 2 BEAMS DESIGNATED AS B6 AND B7. INCLUDE THESE BEAMS IN THE CALCULATIONS.
23. SHEET S4.1; DETAIL 103: REARRANGE THE DETAIL NOTES.
24. SHEET S5.1; DETAIL 201: ADD THE SPACING OF THE NEW 2X4'S IN NOTE 2.
25. SHEET S5.1; DETAIL 201: REARRANGE THE DETAIL NOTES.
26. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.