Permit Number: T14CM05174
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM05174
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 4; SHEET S5.0; DETAIL 1: THE WELDS REQUIRED FOR THE TUBE COLUMN TO THE CONNECTOR PLATES (UPPER AND LOWER) WERE NOT INDICATED ON THE DETAIL. PROVIDE.
2. PREVIOUS COMMENT 5; SHEET S5.0; DETAIL 1: PROVIDE AN ENLARGED DETAIL/PLAN TO CLARIFY HOW THE TWO PLATES ARE LOCATED IN REFERENCE TO THE TUBE.
3. PREVIOUS COMMENT 6; SHEET S5.0; CONNECTION DETAIL 2: THE BRACKET ELEVATION STILL INDICATES A 11" X 1'-7" PLATE, WHILE THE WALL SECTION STILL INDICATES A 17" X 11" X 3/8" PLATE. CLARIFY AND REVISE THE DETAIL.
4. GENERAL: REMOVE THE OLD SHEETS AND INSERT THE REVISED DRAWINGS TO CREATE TWO FULL SETS OF FINAL DRAWINGS.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2014 AROMERO4 APPROVAL SHELF Completed
09/17/2014 AROMERO4 OUT TO CUSTOMER Completed
09/17/2014 CPIERCE1 REJECT SHELF Completed