Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM05174
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 4; SHEET S5.0; DETAIL 1: THE WELDS REQUIRED FOR THE TUBE COLUMN TO THE CONNECTOR PLATES (UPPER AND LOWER) WERE NOT INDICATED ON THE DETAIL. PROVIDE. 2. PREVIOUS COMMENT 5; SHEET S5.0; DETAIL 1: PROVIDE AN ENLARGED DETAIL/PLAN TO CLARIFY HOW THE TWO PLATES ARE LOCATED IN REFERENCE TO THE TUBE. 3. PREVIOUS COMMENT 6; SHEET S5.0; CONNECTION DETAIL 2: THE BRACKET ELEVATION STILL INDICATES A 11" X 1'-7" PLATE, WHILE THE WALL SECTION STILL INDICATES A 17" X 11" X 3/8" PLATE. CLARIFY AND REVISE THE DETAIL. 4. GENERAL: REMOVE THE OLD SHEETS AND INSERT THE REVISED DRAWINGS TO CREATE TWO FULL SETS OF FINAL DRAWINGS. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2014 | AROMERO4 | APPROVAL SHELF | Completed |
| 09/17/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 09/17/2014 | CPIERCE1 | REJECT SHELF | Completed |