Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM04928
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/12/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/15/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The distance between the roll-up door and the personnel door is only 19-0". This makes it impossible for a 32" diameter duct to be 10'-0" away from these two openings in the building. (Note that the location of the paint booth exhaust duct conflicts with the rain water downspout also.) [Initial comment: Verify that the exhaust duct for the paint booth is more than 10-feet from operable openings in the building. Reference: Section 501.3.1 (1), IMC 2012.] |
| 09/15/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/17/2014 | FRODRIG2 | ZONING | REVIEW | Needs Review |