Permit Number: T14CM04928
Parcel: 12419026G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM04928
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/12/2014 JASON GREEN ENGINEERING REVIEW Approved
09/15/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The distance between the roll-up door and the personnel door is only 19-0". This makes it impossible for a 32" diameter duct to be 10'-0" away from these two openings in the building. (Note that the location of the paint booth exhaust duct conflicts with the rain water downspout also.) [Initial comment: Verify that the exhaust duct for the paint booth is more than 10-feet from operable openings in the building. Reference: Section 501.3.1 (1), IMC 2012.]
09/15/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/17/2014 FRODRIG2 ZONING REVIEW Needs Review