Permit Number: T14CM04154
Parcel: 12810069A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM04154
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2014 JASON GREEN ENGINEERING REVIEW Reqs Change Building Plan can not be approved until approval of the DP Package DP14-0086. Building plan will be approved upon approval of the DP. JG
08/26/2014 KEN BROUILLETTE FIRE REVIEW Approved
08/27/2014 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Truly Nolen
T14CM04154
Building Plan (2nd Review)

TRANSMITTAL DATE: August 27, 2014

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.
2. Zoning has reviewed the building plans but cannot approve until a development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/04/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/05/2014 ROBERT SHERRY WATER REVIEW Completed
09/05/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the building design with the component descriptions shown in Section 3 of the Envelope Compliance Certificate (e.g. the roof has R19 cavity insulation, not R-38 cavity insulation. Provide the NFRC certification data for the skylights, windows, and glass doors (see footnote (c) on Section 3 of the Envelope Compliance Certificate. [Initial comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.]
09/05/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the flow direction for sanitary sewer branch 8578-01. According to GIS map data, the branch flows north to manhole 8578-02. If true, then manhole 8578-01, with a rim elevation of approximately 2572 feet, is the upstream manhole, not 8578-02. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole cover. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.]