Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM03857
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2014 | LMAKUS1 | ZONING | REVIEW | Passed | Outside City Limits |
| 06/23/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the envelope compliance certificate to provide a valid analysis of the energy compliance for the building. 2. Specify the height above grade of the termiation of the welding hood exhaust. 3. Clarify how the infra red heaters are to be mounted 14' AFF with 20" clear above the heaters. |
| 06/23/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 06/23/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter and show its location on the site plan. |
| 06/23/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/23/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/23/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the gutter dimensions and the roof areas each gutter drains. |
| 06/23/2014 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | MISSING LETTERS ON SHEET A0.1 PLEASE PROVIDE SCOPE OF WORK ON PROJECT PROVIDE HMIS FOR ALL HAZARDOUS MATERIALS STORED AND USED INSIDE FACILITY. OCCUPANT LOADS DO NOT MATCH ON PLANS |
| 06/23/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/25/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |