Permit Number: T14CM03857
Parcel: 10808001B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03857
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2014 LMAKUS1 ZONING REVIEW Passed Outside City Limits
06/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the envelope compliance certificate to provide a valid analysis of the energy compliance for the building.
2. Specify the height above grade of the termiation of the welding hood exhaust.
3. Clarify how the infra red heaters are to be mounted 14' AFF with 20" clear above the heaters.
06/23/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
06/23/2014 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter and show its location on the site plan.
06/23/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
06/23/2014 LOREN MAKUS ENGINEERING REVIEW Approved
06/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the gutter dimensions and the roof areas each gutter drains.
06/23/2014 KEN BROUILLETTE FIRE REVIEW Reqs Change MISSING LETTERS ON SHEET A0.1
PLEASE PROVIDE SCOPE OF WORK ON PROJECT
PROVIDE HMIS FOR ALL HAZARDOUS MATERIALS STORED AND USED INSIDE FACILITY.
OCCUPANT LOADS DO NOT MATCH ON PLANS
06/23/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/25/2014 SPOWELL1 WWM REVIEW Needs Review