Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM03368
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the size of the existing main natural gas pipe serving 1233 CFH at 90 feet from 2" to 2-1/2" per Table 402.4 (2). Reference: Section 402.4, IFGC 2012. |
| 06/17/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 2. Show that the relocated rooftop unit, AC-1, meets the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012. 3. Show that the thermostat for AC-1 meets the control requirements of Sections C403.2.4 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012. 4. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. 5. Clarify the source of the occupant density, the OSA per person and the OSA per square foot used in the ventilation calculations for the bar server area and for the cashier and salad bar. Revise the occupant density for the bar per Table 403.3, IMC 2012. Reference: Section 403.3, IMC 2012. 6. Revise the ventilation calculations to include an air distribution effectiveness value of 0.8 (ceiling supply, ceiling return, warm air greater than 15 degrees Fahrenheit above space temperature). Reference: Section 403.3.1.2, IMC 2012. 7. Calculation of the required minimum ventilation for air handlers serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.2.3.1 through 403.3.2.3.4, IMC 2012. Reference: section 403.3.2.3, IMC 2012. 8. Verify the balancing data for AC-1: 2000 CFM is scheduled but 2200 CFM is shown on the plans. Reference: Section 403.7, IMC 2012. 9. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012. 10. The architectural plans indicate that the wall behind the Type I hood has been built using wood studs. If the specified hood is not listed for zero-clearance to combustibles, show how the hood installation will be revised to comply with Section 507.9, IMC 2012 for clearances. |
| 06/17/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Tucson Water limits a 5/8" meter to a maximum demand of 15 GPM. Show that the connected fixtures and appliances have a total demand of 15 GPM or less. 2. Provide the size of the reduced pressure backflow preventer along with the size and material of the water service pipe. |
| 06/26/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |