Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM03366
Parcel: 127035560

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03366
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET A-2.0a
1. The following doors are non compliant with ICC A117.1, Section 404.2.3.2: 134, 106a*, 110 and 115.
2. Provide an accessible shower than complies with ICC A117.1, Section 606.2.1 for room 147.
SHEET A-2.0b
3. Reference comment 1 for the following doors: 133* and 141.
SHEET A2.8
4. At detail AG-2, provide a 2'-10" AFF dimension for both lavatories shown.
SHEET A-6.2
5. At detail AP9 and 10, oprovide a dimension of 17" to 19" for the water closet seat height.
6. Provide a 38" to 43" dimension for the standing person spout height.
SHEET A7.0
7. At detail A20, detectable warnings strips are required only at transportation platforms.
END OF REVIEW
06/23/2014 ROBERT SHERRY WATER REVIEW Approved
06/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Complete the waste and vent isometrics: label all of the pipe sizes. Reference: Section 107.2.1, IBC 2012.
2. Show the source of the water for appliance P5A; no connection to the water distribution system is shown on the water isometric. Reference: Section 107.2.1, IBC 2012.
3. Provide automatic faucets for the restroom lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
4. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
5. Verify that the pipe sizes called out for the flush valve and the bedpan washer for the clinical sink will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping) and that the supply pressure to the sink complies with the manufacturer's requirement. Reference: Section 604.3, IPC 2012.
6. Install the waste piping for the clinical sink per the manufacturer's requirements (minimum 3", 4" preferred) and coordinate the vent size shown on the fixture schedule with the waste and vent isometric. Reference: Sections 303.2, 422.6, and 704.2, IPC 2012
7. All healthcare related devices and equipment shall discharge to the building drainage system utilizing an air gap, not air break. Reference: Section 802.1, IPC 2012.
8. The backflow prevention device specified for the Home Hemo Valve Box is listed for use in non-health applications (Low hazard, backpressure and back siphonage, ASSE 1012). Provide a backflow prevention device or assembly rated for the application (e.g. ASSE 1013). Reference: Table 608.1, IPC 2012.
9. Indirect waste receptors shall not be installed in a closet or cupboard, or unventilated space. Reference: Section 802.3, IPC 2012.
10. Complete the design of the natural gas distribution system, showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012.Verify the available gas service pressure; Southwest Gas generally will provide service only at 7"WC, 2 PSIG, or 5PSIG. Reference: Section 107.2.1, IBC 2012.
06/24/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
2. Clarify the reason for the motorized bypass dampers and how ventilation of the individual rooms is affected. Reference: Section 107.2.1, IBC 2012 and Section 401.3, IMC 2012.
06/26/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/03/2014 SHANAE POWELL OUT TO CUSTOMER Completed
07/03/2014 CPIERCE1 REJECT SHELF Completed