Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/01/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
05/01/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
05/01/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEETS A1 (KEYNOTE 3) AND A7 (KEYNOTE 2): PROVIDE A DETAIL AT THE LINTEL REQUIRED OVER THE AREA OF WALL WHERE THE MASONRY IS REMOVED. 2. SHEETS A2 (KEYNOTE 9) AND A4: PROVIDE STRUCTURAL CALCULATIONS FOR THE PLATFORM DESIGN. 3. SHEET A4: PROVIDE STRUCTURAL CALCULATIONS FOR THE CEILING JOIST DESIGN. 4. GENERAL: PROVIDE A SPECIAL INSPECTION FORM FOR FIELD WELDING. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
05/01/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/02/2014 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
05/02/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
05/02/2014 | LHANLY1 | WATER | REVIEW | Completed | |
05/02/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/02/2014 | LHANLY1 | WWM | REVIEW | Passed | |
05/02/2014 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Completed |