Permit Number: T14CM01459
Parcel: 117041900

Address:
127 W 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM01459
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2014 MARTIN BROWN FIRE REVIEW Approved 1)The existing loading/delivery ramp is noted as a 1:9 slope.
Per Section 1104.14 of the 2012 IFC this ramp shall not a running slope steeper than 1 unit vertical in 10 units horizontal. (10%) This ramp is indicated at 1:9 which is a 11.1% slope.

2. Sheet E2.0 has not been corrected under General Note A as requested nor has this previous correction item been addressed in the response from the applicant. Ken B.
08/01/2014 JASON GREEN ENGINEERING REVIEW Approved DATE: August 1, 2014
REVIEWER: Jason Green, CFM
ACTIVITY: T14CM01459 (Building Plan) & T14OT00302 (Floodplain Use Permit)

SUMMARY: Engineering Division of Planning & Development Services Department has received the building plan (T14CM014594) & Floodplain Use Permit (T14OT00302). Engineering Division does not recommend approval of the building plan applications at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan Package (DP13-0234). Please submit a copy of the stamped approved Development Plan Package with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance and the Floodplain Use Permit will be conditioned at that time. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the revised building plan. Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
08/01/2014 JASON GREEN ENGINEERING REVIEW Approved August 8, 2014
FLOODPLAIN USE PERMIT #: T13OT00302
PROJECT ADDRESS: 127 W 5th St
APPLICANT'S NAME: Nancy Bender
PROPERTY OWNER: Whistle Stop Depot LLC

The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone AE floodplain per the Flood Insurance Rate Map Panel #04019C2276L, specifically described as:

Parcel 117-04-1900; Tucson That PT W2 BLK LYG N SP RR BLK 56

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following 8 conditions apply to this permit:
1) This permit becomes invalid and is subject to additional floodplain review, if any required development changes or further disturbance within the floodplain area occurs other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from the construction activity within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.
2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
3) All work shall conform to the approved Development Plan Package and Building Plan prepared by WLFA & Associates LLC which is made part of this permit.
4) The permit is for the change of use from a storage building to an assembly use to a conforming building per the Elevation Certification submitted under T08OT00769 and T08CM00679.
5) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.
6) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.
7) There shall be no stockpiling material, or storage of vehicles, other than that which is accepted by COT and as shown on the approved plans. There shall be no stockpiling or disturbance outside of disturbance limits. Construction material and vehicles shall be promptly removed once improvements are complete.
8) See the associated activity T14CM01459.

This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning and Development Services Department, and Engineering Division.


APPLICANT: Nancy Bender
ADDRESS: 6473 N Foothills Dr Tucson, Arizona 85718
PHONE: (520) 271-7605


(EXPIRATION DATE) Month: 08 Day: 08 Year: 2015

SIGNATURE OF APPLICANT DATE


The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
08/04/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THE DEVELOPMENT PACKAGE AND REQUIRED PARKING SPACES ARE NOT RELATED TO THE OCCUPANCY LOAD AND PLUMBING FIXTURE COUNT.
2. GENERAL: THE ACTUAL BUILDING OCCUPANCY HAS NOT BEEN DETERMINED OR APPROVED AT THIS POINT. IN A NOTE FROM THE MEETING HELD ON DECEMBER 30, 2013 (AND STATED ON THE LATEST SET OF REVISED DRAWINGS), A STATEMENT IS MADE INDICATING "THE BUILDING OCCUPANCY FOR TOILET ROOM COUNT IS BASED ON AN AGREED TYPICAL OCCUPANCY NOT RELATED TO FIRE SAFETY BUT OF NOT EXCEEDING 260 PERSONS FOR THE PURPOSES OF DETERMINING FIXTURE COUNT". THE ACTUAL OCCUPANCY LOAD OF 344 AS LISTED ON THE DRAWINGS CAN NOT BE CHANGED WITHOUT AN APPROVED APPEAL BY THE BUILDING OFFICIAL. PROVIDE THAT APPROVED APPEAL.
3. GENERAL: THE PUBLIC USE DECK (2120 SF) MUST BE INCLUDED IN THE TOTAL BUILDING SQUARE FOOTAGE, THUS ADDING 141 OCCUPANTS TO THE 344 OCCUPANTS. REVISE AND VERIFY THE PLUMBING FIXTURE COUNT. THIS WILL ADDITIONALLY REQUIRE AN APPEAL TO THE BUILDIING OFFICIAL TO TREAT THIS AREA AS AN EXITING AREA ONLY WITH NO ADDITIONAL OCCUPANCY COUNT.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/11/2014 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: T14CM01459
127 W 5th Street
Building Plans

TRANSMITTAL DATE: August 11, 2014

DUE DATE: August 25, 2014

COMMENTS: Building plans need to be revised, see comments.

01. Zoning has reviewed the building plans for compliance with the approved development package.

02. The approved DP was revised to include Bicycle parking facilities within the building. The bicycle facilities shall be drawn, labeled and dimensioned on the building plans. The location and number of facilities must match what was approved on the DP. Provide construction detail drawings of the secure area for the bicycle parking facility.

03. The revisions are minimal and zoning is willing to review and approve the revised building plans over the counter with an appointment by calling in ahead of time to set up a time for the review. Or verify when the reviewer is at the counter.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Site Plan and floorplan Drawings
08/13/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/13/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an approved appeal to the building official verifying the acceptable occupant density. [Initial comment: Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for A2 occupancy (e.g. drinking fountain). Drinking fountains shall also comply with the requirements of Section 410.1, IPC 2012 for approvals and Section 410.2, IPC 2012 and Section 1109.5.1, IBC 2012 for the minimum acceptable number of drinking fountains.]
2. Provide an approved appeal to the building official allowing the proposed fixture arrangement. [Initial comment: For public toilet facilities, the required lavatory shall be located in the same room as the water closet. Reference: Section 405.3.2, IPC 2012.]
08/13/2014 ROBERT SHERRY WATER REVIEW Completed
08/15/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change New comment. All site lighting, except under canopy, appears to have been eliminated from the proposed plans. Provide photometric data showing that emergency egress lighting requirements have been met for the site. Reference IBC sections 1006.1, 1004.5, 1027.5