Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01459
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/17/2014 | DAVID RIVERA | ZONING | REVIEW | Denied | |
| 03/17/2014 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | DATE: March 17, 2014 REVIEWER: Jason Green, CFM ACTIVITY: T14CM01459 (Building Plan) & T14OT00302 (Floodplain Use Permit) SUMMARY: Engineering Division of Planning & Development Services Department has received the building plan (T14CM014594) & Floodplain Use Permit (T14OT00302). Engineering Division does not recommend approval of the building plan applications at this time. The following items need to be addressed: BUILDING PLAN COMMENTS: 1) The building plan application that was submitted is for a Tenant Improvement and as such is only for approval of proposed improvements to the inside of the existing building. Per the submitted building plan sheets there is work that is shown outside of the building footprint that should be part of a site plan review. The development plan package, DP13-0243, which was submitted for all site improvements has not been approved by PDSD therefore should not be shown on the proposed building plan sheets. For building permit approval and for all proposed work inside the existing building revise the sheets to remove the handicap access ramp and handicap parking spaces that are shown along the front of the building. Also remove the development plan package sheets since they are not required as part of the interior remodel and they are not approved at this time. 2) Engineering will re-review the building plan on the next submittal to insure compliance and the Floodplain Use Permit will be conditioned at that time. Additional comments may be forthcoming. GENERAL COMMENTS: Please provide the revised building plan. Further comments may be generated upon resubmittal of the building plan review. For questions or to schedule an appointment I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Planning & Development Services |
| 03/18/2014 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please indicate the second code compliant exit from the Public Use Deck. Is the public use deck having seating or standing associated with the use? Is the deck just being used for egress from inside of the building? If seating or standing will be occuring, then an occupant load calculation should be addressed for this area. Please correct sheet E2.0 under General Note A. This Group A occupancy is over 300 occupant load and is required to have an approved manual fire alarm system per IBC/IFC 907.2.1. Please provide any proposed seating plans for the inside use as required in Section 408.2.1 of the 2012 IFC. |
| 03/21/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; FLOOR PLAN: KEYNOTE 21 INDICATES A "PORTABLE DRINKING DISPENSER'. A SINGLE POINT-OF-USE DISPENSER OR A HIGH/LOW DRINKING FOUNTAIN IS ALLOWED, BUT THEY MUST CONNECT DIRECTLY INTO A WATER LINE. INDICATE ON A PLUMBING DRAWING THIS NEW WATER LINE AND SPECIFY THE DISPENSER/FOUNTAIN. 2. SHEET A1; BUILDING CODE DATA AND OCCUPANCY CALCULATIONS: THE PUBLIC USE DECK (2120 SF) MUST BE INCLUDED IN THE TOTAL BUILDING SQUARE FOOTAGE, THUS ADDING 141 OCCUPANTS TO THE 344 OCCUPANTS. REVISE AND VERIFY THE PLUMBING FIXTURE COUNT. 3. SHEET A1; FLOOR PLAN: THERE IS ONLY ONE EXIT FROM THE BUILDING/DECK. THE DELIVERY RAMP CAN NOT BE USED AS AN EXIT RAMP. LOCATE A NEW STAIR FOR EXITING AS DISCUSSED. 4. SHEET A1; FLOOR PLAN: KEYNOTE 16 INDICATES A URINAL TROUGH. WHERE IS THIS LOCATED? VERIFY. 5. SHEET C-2; KEYNOTE 25: THE RESTROOM CAN NOT BE REFERENCED AS 'FUTURE'. AS DISCUSSED, IT MUST BE INCLUDED AS PART OF THIS PERMIT. 6. SHEET C-2: THE DEVELOPMENT PACKAGE (DP13-0243) MUST BE APPROVED BEFORE THE TENANT IMPROVEMENT CAN BE APPROVED AS DISCUSSED. 7. SHEET C-2; SITE PLAN: IT APPEARS THE ACCESSIBLE ROUTE FROM THE PARKING LOT TO THE BUILDING GOES TO THE DELIVERY RAMP. SEE NOTE 3. 8. GENERAL: THE BUILDING OFFICIAL INDICATED ON HIS EMAIL DATED FEBRUARY 20, 2014, THAT AN APPEAL WOULD BE REQUIRED TO SUBSTANTIATE THE PLUMBING FIXTURE COUNT FOR 300 OCCUPANTS WHEN THE ACTUAL CALCULATED OCCUPANCY LOAD IS 344 (NOW 485 INCLUDING THE PUBLIC USE DECK). PROVIDE THAT APPEAL TO RON BOOSE. 9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/31/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating load calculations that justify the capacities of the heating equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 2. Provide calculations to show how natural ventilation has been provided. Reference: Section 402.1, IMC 2012. 3. Provide balancing information for the restroom exhaust fans. Reference: Section 403.2.1 (4), IMC 2012. |
| 03/31/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for A2 occupancy (e.g. drinking fountain). Drinking fountains shall also comply with the requirements of Section 410.1, IPC 2012 for approvals and Section 410.2, IPC 2012 and Section 1109.5.1, IBC 2012 for the minimum acceptable number of drinking fountains. 2. The use of trough urinals is prohibited. Reference: Section 401.2, IPC 2012. 3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 4. For public toilet facilities, the required lavatory shall be located in the same room as the water closet. Reference: Section 405.3.2, IPC 2012. 5. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 6. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. 7. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2012. |
| 03/31/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2012. 2. Calculate the water demand for this building and determine if the existing water meter is adequate the serve the demand. Reference: Section 604.5, IPC 2012 |
| 04/03/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide site plan with enough information to verify electrical code compliance with all outdoor light fixtures. (light poles noted in this permit set do not exist) Provide corrected information to show compliance with the current 2012 City of Tucson/Pima County Outdoor Lighting Code. Note that maximum color temperature of 3500K, the inclusion of unshielded lumens under canopies, and modifications to the table for allowed lumens are new to the 2012 OLC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/23/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 07/23/2014 | FERNE RODRIGUEZ | REJECT SHELF | Completed |