Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM01299
Parcel: 14043011A

Address:
7211 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01299
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2014 MARTIN BROWN FIRE REVIEW Denied Please define hanger cllassification per NFPA 409. All requirements for hanger classification must be maintained for the life of the building. Also, please provide sprinkler design criteria (per NFPA 13 and NFPA 409), including current flow data, on the plans.
05/22/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change sheet 2.1.1
1. Detail 1:
a. Provide a handrail on the west side of the ramp.
b. Provide a 5'-0" long concrete landing at the bottom of the ramp.
c. Provide a removable gard rail at the painted step edge nosing
d. All gardrails are to be 42" high as per 2012 IBC, Section 1012.
e. all handrails are to be between 34" and 38" high.
SHEET 6.3.1
2. Details 6a and 6b:
a. Reference comments 1a through 1e above.
b. Show dimensional sizes of all risers.
c. Provide a elevation of the ramp handrail
d. All guards are to comply with 2012 IBC, section 1013.
e. All handrails are to comply with 2012 IBC, Section 1012 and the 2009 ICC A117.1, Sections 405.8 and 505.
END OF REVIEW
05/22/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
05/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the termination of the pumped drain from the evaporative cooler. The plumbing vents may only be used for venting of the plumbing system. Reference: Section 901.3, IPC 2012.
2. Provide drainage calculations for the shed roof along with dimensions for the gutter and downspouts. Reference: Sections 1101 and 1106.6, IPC 2012.
05/23/2014 ROBERT SHERRY WATER REVIEW Approved
05/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the addition to the building envelope. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
2. Provide heating load calculations that justify the capacities of the heating equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
3. Provide calculations demonstrating adequate ventilation and exhaust flow rates for the occupancy-type (e.g. education, wood/metal shop per Table 403.3, IMC 2012) of the addition. Reference: Section 403.2, IMC 2012.
06/02/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) The City of Tucson Outdoor Lighting code limits all outdoor lighting to a maximum color temperature of 3500K. Noted "L3" fixtures exceed this. Reference section 402.1 of Outdoor Lighting Code.
2) Noted "L2" fixtures are not full cut-off fixture and are therefore subject to the lumen cap requirements of Table 401.1 and the plan submittal requirements of section 102.4.2 of the OLC which means a complete lighting inventory for the site. Please note that if these fixtures were full cut-off luminaires then they would not be counted per 401.2.1(3) of OLC.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2014 SHANAE POWELL OUT TO CUSTOMER Completed
06/09/2014 CPIERCE1 REJECT SHELF Completed