Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T14CM01181
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/07/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Culver's @ The Bridges T14CM01181 Building Plan (1st Review) TRANSMITTAL DATE: March 7, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans for compliance with the development package but until the development package has been approved zoning cannot approve the building plan. 3. The development package sheets provided in the building plan set need to be the approved development package sheets or clearly marked as reference only on each sheet. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 03/10/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. Provide completed two part certification of special inspectors form. 2. Provide structural calculations and details for all roof top mounted HVAC equipment. 3. Provide structural calculations and details for all the suspended exhaust hoods. 4. Provide structural calculations and details for all electrical pole mounted fixture foundations. SHEETS T1.0 5. Change occupancy classification from "B" to "F-1", two places. SHEETS T1.1 AND T1.2 6. Delete these sheets in their entirety. If accessible details must be copied from the required accessible code manual, please use the requirements from the 2012 IBC, Chapter 11 and the 2009 ICC A117.1. SHEET A1.1 7. Provide an up dated site plan. SHEET A2.0 8. At detail 19, Exiting Plan: a. Show estimated number of occupants exiting through each required exit door and/or gate. b. If more than 50 occupants are exiting through the courtyard, please provide two exits and panic hardware on all gates. SOME WHERE BETWEEN SHEETS 4.1 THROUGH 4.3 9. Please provide a wall section/s through the exhaust hood/s (as necessary) showing all structural supports for the hood and wall make up as per code requirements. SHEET A5.0 10. Delete the ADAAG reference in note 5. SHEET A5.1 11. Review all the accessibility requirements noted and shown on this drawing as to their compliance with the governing accessibility building code, 2012 IBC, Chapter 11 and 2009 ICC A 117.1 and make necessary changes and resubmit. a. Note 11 is out of date. 12. Show required water closets clearance. 13. At note 21, delete the ADA reference. Insure all accessibility requirements and dimensions are as per the governing accessibility code, 2012 IBC, Chapter 11 and 2009 ICC A117.1. SHEET A6.0 14. Review all accessibility requirements and dimensions are as per the governing accessibility code, 2012 IBC, Chapter 11 and 2009 ICC A117.1. Make all changes as required and resubmit. END OF REVIEW |
| 03/11/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 03/19/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater (e.g. the fryers according to detail5/P4.1) will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Show the proposed location of the regulator on the plans. Reference: Section 402.1, IFGC 2012. 2. Coordinate the equipment marks with the mechanical plans (i.e. units RTU-1 and RTU-2 are labeled as two RTU-1 units on the gas isometric and RTU-1 is labeled as AC-1 on sheet P1.1). 3. Clarify keynote 1 on sheet P1.1. PVC is not approved for use in a water distribution system within a building. Reference: Section 605.4, IPC 2012. 4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (the specified dual-check valve with intermediate vent, Watts 9DM, is not a pressure-absorbing device). Reference: Section 604.9, IPC 2012. 5. Provide a full-open valve for the water service at the building entrance. Reference: Section 606.1(2), IPC 2012. 6. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson. |
| 03/19/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/20/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing (e.g. COMcheck shows the roof with R38 cavity insulation but the sections on A4.0, A4.1, A4.2, and A4.3 call out R30 cavity insulation, similarly the glazing specification on sheet A5.0 does not agree with the COMcheck figures for U-value and SHGC). Show the specified U-values and, as appropriate, the SHGC values for the doors on the plans. Reference: Section C303.1, IECC 2012, as amended by the City of Tucson. 2. The City of Tucson has not adopted ASHRAE Standard 62.1as an approved method for calculating ventilation requirements; use the methods shown in Section 403, IMC 2012 to determine the minimum required amount of mechanical ventilation. Reference: Section 401.2, IMC 2012 and Section C403.2.5, IECC 2012. 3. All drawings and documents submitted to the City of Tucson for the purpose of obtaining a building permit become items of public record once the permit is issued. The proprietary notices on the Accurex shop drawings indicate that the shop drawings contain confidential and trade secret information that is not to be reproduced without the written consent of Accurex. Remove the proprietary shop drawings from the drawing set and include only the information required to show that the proposed Type I and Type II hoods will comply with all code requirements such as salient dimensions, listings, features (e.g. filters, grease collection, etc), installation details, and balancing data). |
| 03/21/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1) Provide engineering calculations and details for light-pole bases. These may be included in either the structural sheets or the electrical sheets. 2) Provide cut-sheets for all exterior luminaires indicating lamp type to be installed, total lumen output per luminaire, and color temperature. One of your indicated lamps has a color temperature of 4000K, the City of Tucson Outdoor Lighting Code limits the color temp to 3500K. 3) PP E1.0 indicates that all exterior lighting is to be full cutoff. Provide cut-sheets indicating how the LED lightbands meet this requirement. 4) PP E4.1 has a proprietary notice concerning trade secret information. When the City of Tucson issues a permit then all plan sheets become public information. Please only provide such information as is necessary for plan review and remove any trade secret information from the plan set. 5) Two circuits in panel "A" have been specified for the hand dryer in the women's restroom. Floor plan specifies ckt 34 -- is ckt 40 meant for the employee restroom? 6) Could not locate Custard Dipping Cabinet (equip note 75, pnl A ckt 3) on power plans 7) Could not locate mister pump (pnl A2 ckt 20), or irrigation controller (pnl A2 ckt 38) on power plans 8) Could not locate any device using pnl A2 ckt 42, and identified as Ice machine 115, on power plans 9) Panel "B" could not locate kitchen ice maker 89A (ckt 7), receptacles (ckt 35), microwave (ckt 37) or warmers (ckts 8,10,38) on power plan. 10) Panel "C" ckt 20, waffle cone maker 87, could not be located on power plan. 11) Panel "D" ckt's 6, 34, 36, 38 could be found as part of equipment on power plans. |
| 03/24/2014 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Needs Review | EOR stated GP was coming in so wait to approve bldg plans; Runner requests denial to generate next workflow. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/11/2014 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 04/11/2014 | CPIERCE1 | REJECT SHELF | Completed |