| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Cleanfreak $3 Carwash T14CM01004 Building Plan (2nd Review) TRANSMITTAL DATE: May 5, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans but cannot approve until the development package has been approved for the site change 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 05/07/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 05/08/2014 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | Building plan will be approved upon approval of the DP14-0029. JG |
| 05/12/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/14/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify how exterior wall #2 in the Envelope Compliance Certificate is to be built and show this on the drawings; the description states that the wall will have R-1.1 cavity insulation and R-20 continuous insulation. In addition, the roof is described as having R-38 cavity insulation but it is not indicated on the drawings. [Initial comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.] 2. Provide a copy of the manufacturer's description of the features for the proposed programmable thermostat. [Initial comment: Verify that the specified controls provide the capabilities noted in the COMcheck Generic Requirements #5 and #6 on sheet M2.0. Reference: Section C403.2.4, IECC 2012.] |
| 05/14/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Neither the architectural nor the structural drawings provided details to show how the water heater shelf is to be attached to the building structure "…as appropriate." [Initial comment: Provide structural calculations and details to show how the proposed water heater support is to be connected to the building structure. Reference: Section 301.2, IPC 2012.] 2. Based on your response, the rim elevation of the next upstream manhole (9918-A64A, 2455.90') is less than 12" below the finished floor elevation of the car wash tunnel (2456.80') and a backwater valve is required for the car wash tunnel. The finished floor elevation for the car wash building is more than 12" above the rim elevation of the next upstream manhole so no backwater valve is required for the car wash building. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/16/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 05/16/2014 | CPIERCE1 | REJECT SHELF | Completed |