| 02/21/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The tower structural calculations require modifications be made in three places of the tower in APPENDIX "D" which are not shown in the construction documents: a. Include the seven drawings detailing the tower modifications to be made in the construction document set and in a 24 x 36 format. b. Show these drawings in the drawing index of sheet T1. c. Show the changes to be made on details 1/A4 and 1/A5 and reference these changes to the structural drawing modifications. END OF REVIEW |
| 02/21/2014 | MICHAEL ST. PAUL | PLANNING-CITY HALL | REVIEW | Approved | |
| 02/21/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/26/2014 | GREGORY MCNEAL | COMMUNICATIONS | REVIEW | Approved | |
| 03/06/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM00925 Antenna Equipment Replacement 1. Identify the electrical load of any proposed equipment, NEC 220. 2. Show the size of circuits used the power proposed equipment and identify any removed loads, NEC 225. Ken Van Karsen Elect Plan Review PDSD, City of Tucson 520-837-4912 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/10/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 03/10/2014 | CPIERCE1 | REJECT SHELF | Completed |