Permit Number: T14CM00885
Parcel: 11310001A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00885
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/28/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/28/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Heating and cooling load calculations not included with submittal. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.]
2. Mechanical details 101, 109, and 110 show the fan coils and ERV units suspended from the structure above with spring isolators. The structural detail 31/S1.3 shows the units sitting on structural members without vibration isolation. Coordinate the details. [Initial comment: Coordinate the support of the fan coil and energy recovery units with the structural details. Reference: Section 302.1, IMC 2012.]
3. Show the exhaust flow rate for the chemical hood exhaust. [Initial comment: Show the exhaust flow rates for the chemical and biological fume hoods. Reference: Section 501.4, IMC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2014 SHANAE POWELL REJECT SHELF Completed